A.5 Protocol-Dependent Functions - Siemens SIPROTEC 7SA522 Manual

Distance protection
Hide thumbs Also See for SIPROTEC 7SA522:
Table of Contents

Advertisement

A.5
Protocol-dependent Functions
Protocol →
IEC 60870-5-103
Function ↓
Operational Mea-
Yes
sured Values
Metered Values
Yes
Fault Recording
Yes
Remote Relay
No. Only via addi-
Setting
tional service inter-
face
User-defined
Yes
Alarms and Switch-
ing Objects
Time Synchronisa-
Via protocol;
tion
DCF77/IRIG B; In-
terface; Binary input
Messages with Time
Yes
Stamp
Commissioning Tools
Alarm and Mea-
Yes
sured Value Trans-
mission Blocking
Generate Test
Yes
Alarms
Physical Mode
Asynchronous
Transmission Mode Cyclic/Event
Baud Rate
4800 to 38400
Type
RS 232 RS 485
Optical fibre
7SA522 Manual
C53000-G1176-C155-3
PROFIBUS FMS
PROFIBUS DP
Yes
Yes
Yes
Yes
Yes
No. Only via addi-
tional service inter-
face
Yes
No. Only via addi-
tional service inter-
face
Yes
Pre-defined "user-
defined messages"
in CFC
Via protocol;
Via DCF77/IRIG B;
DCF77/IRIG B; In-
Interface; Binary
terface; Binary input
input
Yes
No
Yes
No
Yes
No
Asynchronous
Asynchronous
Cyclic/Event
Cyclic
Up to 1.5 MBaud
Up to 1.5 MBaud
RS 485 Optical fibre
RS 485 Optical fibre
Double ring
Double ring

A.5 Protocol-dependent Functions

DNP3.0
Additional In-
terface (op-
tional)
Yes
Yes
Yes
Yes
No. Only via ad-
Yes
ditional service
interface
No. Only via ad-
Yes
ditional service
interface
Pre-defined
Yes
"User-defined
messages" in
CFC
Via protocol;
-
DCF77/IRIG B;
Interface; Binary
input
Yes
Yes
No
Yes
No
Yes
Asynchronous
-
Cyclic/Event
-
2400 to 19200
2400 to
115200
RS 485 Optical
RS232/RS48
fibre
5
527