Directional Blocking Scheme - Siemens SIPROTEC 7SA522 Manual

Distance protection
Hide thumbs Also See for SIPROTEC 7SA522:
Table of Contents

Advertisement

2 Functions
Figure 2-57
Unblock logic
2.6.7

Directional Blocking Scheme

Principle
140
The following scheme is suited for conventional transmission media.
In the case of the blocking scheme, the transmission channel is used to send a block
signal from one line end to the other. The signal may be sent directly after fault incep-
tion (jump detector above dotted line in Figure 2-58), and stopped immediately, as
soon as the distance protection detects a fault in the forward direction, alternatively the
signal is only sent when the distance protection detects the fault in the reverse direc-
tion. It is stopped immediately as soon as the distance protection detects a fault in
forward direction. Tripping is possible with this scheme even if no signal is received
from the opposite line end. It is therefore mainly used for long lines when the signal
must be transmitted across the protected feeder by means of power line carrier (PLC)
7SA522 Manual
C53000-G1176-C155-3

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents