Settings - Siemens SIPROTEC 7SA522 Manual

Distance protection
Hide thumbs Also See for SIPROTEC 7SA522:
Table of Contents

Advertisement

Trip with Delay
2.9.2.3

Settings

Addr.
Parameter
2501
FCT Weak Infeed
2502A
Trip/Echo DELAY
2503A
Trip EXTENSION
2504A
Echo BLOCK Time
2505
UNDERVOLTAGE
2509
Echo:1channel
2510
Uphe< Factor
7SA522 Manual
C53000-G1176-C155-3
In address  :, QRQ GHOD\HG the stage for instantaneous tripping is switched
2)) or 21 continuously.
The operation of the delayed tripping is determined by three parameters:
• Address  SRO 7ULS enables a single-pole trip command in case of single-
pole faults if set to 21.
• If set to 21, address  SRO ZLWK , allows a single-pole trip command
only if the threshold ,! 7KUHVKROG for the zero current has been surpassed.
Position 2)) allows a single-pole trip command even when ,! 7KUHVKROG is
not exceeded. The time delay of "3I0> exceeded" is set at address  7 ,!
([W.
• If set to 21, address  SRO 7ULS allows also a three-pole trip command. In
position 2)) the multi-pole pickup is only reported but a three-pole trip command is
not issued (only report). But a single-pole trip command can nevertheless be
issued.
A delayed tripping stage is implemented to allow tripping the dedicated line end in
case the transmission channel is faulted. When undervoltage conditions have been
detected, this stage picks up in one or more phases and after a configured time (ad-
dress  70 and address  77) has elapsed it trips without delay.
The delayed-tripping stage :, GHOD\HG is switched 21 or 2)) - permanently at
address . The setting E\ UHFHLYH IDLO only activates this stage if ´!:, UHF
2.µ is not reported as OFF.
To avoid erroneous pickup, phase selection via undervoltage is blocked entirely in the
event of voltage failure (pickup of the fuse failure monitor or of the VT mcb). Moreover
the corresponding phases are equally blocked if another protection function, capable
to detect faults, picks up.
Addresses which have an appended "A" can only be changed with DIGSI, under Ad-
ditional Settings.
The table indicates region-specific presettings. Column C (configuration) indicates the
corresponding secondary nominal current of the current transformer.
C
Setting Options
OFF
ECHO only
ECHO and TRIP
0.00 .. 30.00 sec
0.00 .. 30.00 sec
0.00 .. 30.00 sec
2 .. 70 V
NO
YES
0.10 .. 1.00
2.9.2 Tripping According to French Specification
Default Setting
ECHO only
Weak Infeed function is
0.04 sec
Trip / Echo Delay after
carrier receipt
0.05 sec
Trip Extension / Echo
Impulse time
0.05 sec
Echo Block Time
25 V
Undervoltage (ph-e)
NO
Echo logic: Dis and EF on
common channel
0.70
Factor for undervoltage
Uphe<
Comments
203