A Appendix
Addr.
Parameter
3774
U1<<
3775
T U1<<
3778
CURR.SUP.U1<
3802
START
3805
Paral.Line Comp
3806
Load Compensat.
3901
FCT BreakerFail
3902
I> BF
3903
1p-RETRIP (T1)
3904
T1-1pole
3905
T1-3pole
3906
T2
3907
T3-BkrDefective
3908
Trip BkrDefect.
3909
Chk BRK CONTACT
3921
End Flt. stage
3922
T-EndFault
3931
PoleDiscrepancy
3932
T-PoleDiscrep.
4001
FCT TripSuperv.
4002
No. of BI
4003
Alarm Delay
4501
STATE PROT I 1
4502
CONNEC. 1 OVER
4505A
PROT 1 T-DELAY
4509
T-DATA DISTURB
4510
T-DATAFAIL
4511
Td ResetRemote
4601
STATE PROT I 2
4602
CONNEC. 2 OVER
4605A
PROT 2 T-DELAY
4701
ID OF RELAY 1
4702
ID OF RELAY 2
544
Function
C
Setting Options
Voltage Prot.
1.0 .. 100.0 V; 0
0.00 .. 100.00 sec; ∞
Voltage Prot.
Voltage Prot.
ON
OFF
Fault Locator
Pickup
TRIP
Fault Locator
NO
YES
Fault Locator
NO
YES
Breaker Failure
ON
OFF
Breaker Failure
1A
0.05 .. 20.00 A
5A
0.25 .. 100.00 A
Breaker Failure
NO
YES
0.00 .. 30.00 sec; ∞
Breaker Failure
0.00 .. 30.00 sec; ∞
Breaker Failure
0.00 .. 30.00 sec; ∞
Breaker Failure
0.00 .. 30.00 sec; ∞
Breaker Failure
Breaker Failure
NO
with T1-trip
with T2-trip
w/ T1/T2-trip
Breaker Failure
NO
YES
Breaker Failure
ON
OFF
0.00 .. 30.00 sec; ∞
Breaker Failure
Breaker Failure
ON
OFF
0.00 .. 30.00 sec; ∞
Breaker Failure
TripCirc.Superv
ON
OFF
TripCirc.Superv
1 .. 2
TripCirc.Superv
1 .. 30 sec
Prot. Interface
ON
OFF
Prot. Interface
F.optic direct
Com conv 64 kB
Com conv 128 kB
Com conv 512 kB
Prot. Interface
0.1 .. 30.0 ms
Prot. Interface
0.05 .. 2.00 sec
Prot. Interface
0.0 .. 60.0 sec
0.00 .. 300.00 sec; ∞
Prot. Interface
Prot. Interface
ON
OFF
Prot. Interface
F.optic direct
Com conv 64 kB
Com conv 128 kB
Com conv 512 kB
Prot. Interface
0.1 .. 30.0 ms
Prot. Interface
1 .. 65534
Prot. Interface
1 .. 65534
Default Setting
10.0 V
U1<< Pickup
1.00 sec
T U1<< Time Delay
ON
Current supervision (U1)
Pickup
Start fault locator with
YES
Mutual coupling parall.line com-
pensation
NO
Load Compensation
ON
Breaker Failure Protection is
0.10 A
Pick-up threshold I>
0.50 A
YES
1pole retrip with stage T1 (local
trip)
0.00 sec
T1, Delay after 1pole start (local
trip)
0.00 sec
T1, Delay after 3pole start (local
trip)
0.15 sec
T2, Delay of 2nd stage (busbar trip)
0.00 sec
T3, Delay for start with defective
bkr.
NO
Trip output selection with defective
bkr
YES
Check Breaker contacts
OFF
End fault stage is
2.00 sec
Trip delay of end fault stage
OFF
Pole Discrepancy supervision
2.00 sec
Trip delay with pole discrepancy
OFF
TRIP Circuit Supervision is
2
Number of Binary Inputs per trip
circuit
2 sec
Delay Time for alarm
ON
State of protection interface 1
F.optic direct
Connection 1 over
30.0 ms
Prot 1: Maximal permissible delay
time
0.10 sec
Time delay for data disturbance
alarm
6.0 sec
Time del for transmission failure
alarm
0.00 sec
Remote signal RESET DELAY for
comm.fail
ON
State of protection interface 2
F.optic direct
Connection 2 over
30.0 ms
Prot 2: Maximal permissible delay
time
1
Identification number of relay 1
2
Identification number of relay 2
Comments
7SA522 Manual
C53000-G1176-C155-3