Siemens SIPROTEC 7SA522 Manual page 266

Distance protection
Hide thumbs Also See for SIPROTEC 7SA522:
Table of Contents

Advertisement

2 Functions
Synchronism
Check Conditions
before Manual
Closing
266
Addresses  to  are relevant to the check conditions before manual closure
and closing via control command of the circuit breaker. When setting the general pro-
tection data (Power System Data 2, Section 2.1.5.1) it was already decided at address
 whether synchronism and voltage check should be carried out before manual
closing. With the following setting in address 0$1 &/26( = ZR 6\QFFKHFN, no
checks are performed before manual closing.
Address  6\QF&% determines for commands via the integrated control function
(local, DIGSI, serial interface) whether synchronism check is carried out or not. This
address also tells the device for which switching device of the control the synchronism
check applies. You can select from the switching devices which are available for the
integrated control. Choose the circuit breaker to be operated via the synchronism
check. This is usually the circuit breaker which is operated in case of manual closing
or automatic reclosure. If you set 6\QF&% = QRQH here, a CLOSE command via the
integrated control will be carried out without synchronism check.
Address  2SPRGH ZLWK 0& determines whether closing under asynchronous
system conditions is allowed for manual closing or reclosure via control command. Set
this parameter to ZLWK 7&% FORVH to allow asynchronous closing; the relay will
then consider the circuit breaker closing time before determining the correct instant for
the close command. Remember that closing under asynchronous system conditions
is allowed only if the circuit breaker closing time is set correctly (see above under "Pre-
conditions")! If you wish to permit manual closure or closing via control command only
under synchronous system conditions, set this address to ZR 7&% FORVH.
The permissible magnitude difference of the voltages is set at address  0&
PD[9ROW'LII. The setting is applied in Volts secondary. This value can be entered
as a primary value when parameterizing with a PC and DIGSI
nection of the voltages these are phase-to-earth voltages or phase-to-phase voltages.
The permissible frequency difference between the voltages is set at address  0&
PD[)UHT'LII, the permissible phase angle difference at address  0&
PD[$QJOH'LII.
The further release conditions for manual reclosing or reclosure via control command
are set under addresses  to .
The following addresses mean:
 0& 6<1&+5
 0& 8V\Q! 8OLQH
 0& 8V\Q 8OLQH!
 0& 8V\Q 8OLQH
 0& 25,'(
the busbar (Ubus) and the feeder (Uline) must both be
energized (/LYH 9ROW 7KU, address ); the
conditions for synchronism are checked i.e., 0&
PD[9ROW'LII (address ), 0&
PD[)UHT'LII(address ) and 0&
PD[$QJOH'LII (address ); This setting is only
®
possible via DIGSI
under Additional Settings.
the busbar (Ubus) must be live (/LYH 9ROW 7KU,
address ), the feeder (Uline) must be dead ('HDG
9ROW 7KU, address );
the busbar (Ubus) must be dead ('HDG 9ROW 7KU,
address ), the feeder (Uline) must be live (/LYH
9ROW 7KU, address );
the busbar (Ubus) and the feeder (Uline) must both be
de-energized ('HDG 9ROW 7KU, address );
manual closing or closing via control command is re-
leased without any check.
®
. Depending on the con-
7SA522 Manual
C53000-G1176-C155-3