Siemens SIPROTEC 7SA522 Manual page 534

Distance protection
Hide thumbs Also See for SIPROTEC 7SA522:
Table of Contents

Advertisement

A Appendix
Addr.
Parameter
1335
T4 DELAY
1341
Op. mode Z5
1342
R(Z5) Ø-Ø
1343
X(Z5)+
1344
RE(Z5) Ø-E
1345
T5 DELAY
1346
X(Z5)-
1351
Op. mode Z1B
1352
R(Z1B) Ø-Ø
1353
X(Z1B)
1354
RE(Z1B) Ø-E
1355
T1B-1phase
1356
T1B-multi-phase
1357
1st AR -> Z1B
1401
Op. mode Z1
1402
ZR(Z1)
1411
Op. mode Z2
1412
ZR(Z2)
1421
Op. mode Z3
1422
ZR(Z3)
1431
Op. mode Z4
1432
ZR(Z4)
1441
Op. mode Z5
1442
ZR(Z5)
534
Function
C
Setting Options
0.00 .. 30.00 sec; ∞
Dis. General
Dis. Quadril.
Dis. MHO
Dis. Quadril.
Forward
Reverse
Non-Directional
Inactive
0.050 .. 600.000 Ω
Dis. Quadril.
1A
0.010 .. 120.000 Ω
5A
0.050 .. 600.000 Ω
Dis. Quadril.
1A
0.010 .. 120.000 Ω
5A
0.050 .. 600.000 Ω
Dis. Quadril.
1A
0.010 .. 120.000 Ω
5A
0.00 .. 30.00 sec; ∞
Dis. General
Dis. Quadril.
Dis. MHO
0.050 .. 600.000 Ω
Dis. Quadril.
1A
0.010 .. 120.000 Ω
5A
Dis. Quadril.
Forward
Reverse
Non-Directional
Inactive
0.050 .. 600.000 Ω
Dis. Quadril.
1A
0.010 .. 120.000 Ω
5A
0.050 .. 600.000 Ω
Dis. Quadril.
1A
0.010 .. 120.000 Ω
5A
0.050 .. 600.000 Ω
Dis. Quadril.
1A
0.010 .. 120.000 Ω
5A
0.00 .. 30.00 sec; ∞
Dis. General
Dis. Quadril.
Dis. MHO
0.00 .. 30.00 sec; ∞
Dis. General
Dis. Quadril.
Dis. MHO
Dis. General
NO
Dis. Quadril.
YES
Dis. MHO
Dis. MHO
Forward
Reverse
Inactive
0.050 .. 200.000 Ω
Dis. MHO
1A
0.010 .. 40.000 Ω
5A
Dis. MHO
Forward
Reverse
Inactive
0.050 .. 200.000 Ω
Dis. MHO
1A
0.010 .. 40.000 Ω
5A
Dis. MHO
Forward
Reverse
Inactive
0.050 .. 200.000 Ω
Dis. MHO
1A
0.010 .. 40.000 Ω
5A
Dis. MHO
Forward
Reverse
Inactive
0.050 .. 200.000 Ω
Dis. MHO
1A
0.010 .. 40.000 Ω
5A
Dis. MHO
Forward
Reverse
Inactive
0.050 .. 200.000 Ω
Dis. MHO
1A
0.010 .. 40.000 Ω
5A
Default Setting
0.90 sec
T4 delay
Inactive
Operating mode Z5
12.000 Ω
R(Z5), Resistance for ph-ph-faults
2.400 Ω
12.000 Ω
X(Z5)+, Reactance for Forward di-
rection
2.400 Ω
12.000 Ω
RE(Z5), Resistance for ph-e faults
2.400 Ω
0.90 sec
T5 delay
4.000 Ω
X(Z5)-, Reactance for Reverse di-
rection
0.800 Ω
Forward
Operating mode Z1B (overrreach
zone)
1.500 Ω
R(Z1B), Resistance for ph-ph-
faults
0.300 Ω
3.000 Ω
X(Z1B), Reactance
0.600 Ω
3.000 Ω
RE(Z1B), Resistance for ph-e
faults
0.600 Ω
0.00 sec
T1B-1phase, delay for single ph.
faults
0.00 sec
T1B-multi-ph, delay for multi ph.
faults
YES
Z1B enabled before 1st AR (int. or
ext.)
Forward
Operating mode Z1
2.500 Ω
ZR(Z1), Impedance Reach
0.500 Ω
Forward
Operating mode Z2
5.000 Ω
ZR(Z2), Impedance Reach
1.000 Ω
Reverse
Operating mode Z3
5.000 Ω
ZR(Z3), Impedance Reach
1.000 Ω
Forward
Operating mode Z4
10.000 Ω
ZR(Z4), Impedance Reach
2.000 Ω
Inactive
Operating mode Z5
10.000 Ω
ZR(Z5), Impedance Reach
2.000 Ω
Comments
7SA522 Manual
C53000-G1176-C155-3

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents