Siemens SIPROTEC 7SA522 Manual page 533

Distance protection
Hide thumbs Also See for SIPROTEC 7SA522:
Table of Contents

Advertisement

Addr.
Parameter
ϕ load (Ø-Ø)
1244
1301
Op. mode Z1
1302
R(Z1) Ø-Ø
1303
X(Z1)
1304
RE(Z1) Ø-E
1305
T1-1phase
1306
T1-multi-phase
1307
Zone Reduction
1311
Op. mode Z2
1312
R(Z2) Ø-Ø
1313
X(Z2)
1314
RE(Z2) Ø-E
1315
T2-1phase
1316
T2-multi-phase
1317A
Trip 1pole Z2
1321
Op. mode Z3
1322
R(Z3) Ø-Ø
1323
X(Z3)
1324
RE(Z3) Ø-E
1325
T3 DELAY
1331
Op. mode Z4
1332
R(Z4) Ø-Ø
1333
X(Z4)
1334
RE(Z4) Ø-E
7SA522 Manual
C53000-G1176-C155-3
Function
C
Setting Options
20 .. 60 °
Dis. General
Dis. Quadril.
Forward
Reverse
Non-Directional
Inactive
0.050 .. 600.000 Ω
Dis. Quadril.
1A
0.010 .. 120.000 Ω
5A
0.050 .. 600.000 Ω
Dis. Quadril.
1A
0.010 .. 120.000 Ω
5A
0.050 .. 600.000 Ω
Dis. Quadril.
1A
0.010 .. 120.000 Ω
5A
0.00 .. 30.00 sec; ∞
Dis. General
Dis. Quadril.
Dis. MHO
0.00 .. 30.00 sec; ∞
Dis. General
Dis. Quadril.
Dis. MHO
0 .. 45 °
Dis. Quadril.
Dis. Quadril.
Forward
Reverse
Non-Directional
Inactive
0.050 .. 600.000 Ω
Dis. Quadril.
1A
0.010 .. 120.000 Ω
5A
0.050 .. 600.000 Ω
Dis. Quadril.
1A
0.010 .. 120.000 Ω
5A
0.050 .. 600.000 Ω
Dis. Quadril.
1A
0.010 .. 120.000 Ω
5A
0.00 .. 30.00 sec; ∞
Dis. General
Dis. Quadril.
Dis. MHO
0.00 .. 30.00 sec; ∞
Dis. General
Dis. Quadril.
Dis. MHO
Dis. General
NO
Dis. Quadril.
YES
Dis. MHO
Dis. Quadril.
Forward
Reverse
Non-Directional
Inactive
0.050 .. 600.000 Ω
Dis. Quadril.
1A
0.010 .. 120.000 Ω
5A
0.050 .. 600.000 Ω
Dis. Quadril.
1A
0.010 .. 120.000 Ω
5A
0.050 .. 600.000 Ω
Dis. Quadril.
1A
0.010 .. 120.000 Ω
5A
0.00 .. 30.00 sec; ∞
Dis. General
Dis. Quadril.
Dis. MHO
Dis. Quadril.
Forward
Reverse
Non-Directional
Inactive
0.050 .. 600.000 Ω
Dis. Quadril.
1A
0.010 .. 120.000 Ω
5A
0.050 .. 600.000 Ω
Dis. Quadril.
1A
0.010 .. 120.000 Ω
5A
0.050 .. 600.000 Ω
Dis. Quadril.
1A
0.010 .. 120.000 Ω
5A
Default Setting
45 °
PHI load, maximum Load Angle
(ph-ph)
Forward
Operating mode Z1
1.250 Ω
R(Z1), Resistance for ph-ph-faults
0.250 Ω
2.500 Ω
X(Z1), Reactance
0.500 Ω
2.500 Ω
RE(Z1), Resistance for ph-e faults
0.500 Ω
0.00 sec
T1-1phase, delay for single phase
faults
0.00 sec
T1multi-ph, delay for multi phase
faults
0 °
Zone Reduction Angle (load com-
pensation)
Forward
Operating mode Z2
2.500 Ω
R(Z2), Resistance for ph-ph-faults
0.500 Ω
5.000 Ω
X(Z2), Reactance
1.000 Ω
5.000 Ω
RE(Z2), Resistance for ph-e faults
1.000 Ω
0.30 sec
T2-1phase, delay for single phase
faults
0.30 sec
T2multi-ph, delay for multi phase
faults
NO
Single pole trip for faults in Z2
Reverse
Operating mode Z3
5.000 Ω
R(Z3), Resistance for ph-ph-faults
1.000 Ω
10.000 Ω
X(Z3), Reactance
2.000 Ω
10.000 Ω
RE(Z3), Resistance for ph-e faults
2.000 Ω
0.60 sec
T3 delay
Non-Directional
Operating mode Z4
12.000 Ω
R(Z4), Resistance for ph-ph-faults
2.400 Ω
12.000 Ω
X(Z4), Reactance
2.400 Ω
12.000 Ω
RE(Z4), Resistance for ph-e faults
2.400 Ω