Siemens SIPROTEC 7SA522 Manual page 158

Distance protection
Hide thumbs Also See for SIPROTEC 7SA522:
Table of Contents

Advertisement

2 Functions
Figure 2-67
Zero-sequence power protection
Phase Current
Stabilization
158
The power-time characteristic can be displaced in power direction via a reference
(= basic value for the inverse characteristic for ϕ = ϕ
value S
ref
tion by a factor k.
Figure 2-67 shows the logic diagram. The tripping time depends on the level of the
compensated zero sequence power S
systems the zero sequence voltage and the zero sequence current increase towards
the earth fault location. The inverse characteristic results in the shortest command
time for the relay closest to the fault. The other relays then reset.
Non-symmetrical load conditions in multiple-earthed systems or different current
transformer errors can result in a zero sequence current. This zero sequence current
could cause faulty pickup of the earth current stages if low pick-up thresholds are set.
To avoid this, the earth current stages are stabilized by the phase current: As the
phase currents increase, the pick up thresholds are increased (Figure 2-68). The sta-
as defined above. For meshed earthed
r
) and in time direc-
comp
7SA522 Manual
C53000-G1176-C155-3