Information List - Siemens SIPROTEC 7SA522 Manual

Distance protection
Hide thumbs Also See for SIPROTEC 7SA522:
Table of Contents

Advertisement

Addr.
Parameter
3174
BLK for DisZone
3182
3U0>(U0 inv)
3183
U0inv. minimum
3184
T forw. (U0inv)
3185
T rev. (U0inv)
2.7.4

Information List

No.
Information
1305
>EF BLK 3I0>>>
1307
>EF BLOCK 3I0>>
1308
>EF BLOCK 3I0>
1309
>EF BLOCK 3I0p
1310
>EF InstTRIP
1331
E/F Prot. OFF
1332
E/F BLOCK
1333
E/F ACTIVE
1335
EF TRIP BLOCK
1336
E/F L1 selec.
1337
E/F L2 selec.
1338
E/F L3 selec.
1345
EF Pickup
1354
EF 3I0>>>Pickup
1355
EF 3I0>> Pickup
1356
EF 3I0> Pickup
1357
EF 3I0p Pickup
1358
EF forward
1359
EF reverse
1361
EF Trip
1362
E/F Trip L1
1363
E/F Trip L2
1364
E/F Trip L3
1365
E/F Trip 3p
1366
EF 3I0>>> TRIP
1367
EF 3I0>> TRIP
1368
EF 3I0> TRIP
1369
EF 3I0p TRIP
1370
EF InrushPU
7SA522 Manual
C53000-G1176-C155-3
2.7 Earth fault overcurrent protection in earthed systems (optional)
C
Setting Options
in zone Z1
in zone Z1/Z1B
in each zone
1.0 .. 10.0 V
0.1 .. 5.0 V
0.00 .. 32.00 sec
0.00 .. 32.00 sec
Type of In-
formation
SP
>Earth Fault O/C Block 3I0>>>
SP
>Earth Fault O/C Block 3I0>>
SP
>Earth Fault O/C Block 3I0>
SP
>Earth Fault O/C Block 3I0p
SP
>Earth Fault O/C Instantaneous trip
OUT
Earth fault protection is switched OFF
OUT
Earth fault protection is BLOCKED
OUT
Earth fault protection is ACTIVE
OUT
Earth fault protection Trip is blocked
OUT
E/F phase selector L1 selected
OUT
E/F phase selector L2 selected
OUT
E/F phase selector L3 selected
OUT
Earth fault protection PICKED UP
OUT
E/F 3I0>>> PICKED UP
OUT
E/F 3I0>> PICKED UP
OUT
E/F 3I0> PICKED UP
OUT
E/F 3I0p PICKED UP
OUT
E/F picked up FORWARD
OUT
E/F picked up REVERSE
OUT
E/F General TRIP command
OUT
Earth fault protection: Trip 1pole L1
OUT
Earth fault protection: Trip 1pole L2
OUT
Earth fault protection: Trip 1pole L3
OUT
Earth fault protection: Trip 3pole
OUT
E/F 3I0>>> TRIP
OUT
E/F 3I0>> TRIP
OUT
E/F 3I0> TRIP
OUT
E/F 3I0p TRIP
OUT
E/F Inrush picked up
Default Setting
in each zone
Block E/F for Distance Pro-
tection Pickup
5.0 V
3U0> setpoint
0.2 V
Minimum voltage U0min for
T->oo
0.90 sec
T-forward Time delay
(U0inv)
1.20 sec
T-reverse Time delay
(U0inv)
Comments
Comments
175