Siemens SIPROTEC 7SA522 Manual page 536

Distance protection
Hide thumbs Also See for SIPROTEC 7SA522:
Table of Contents

Advertisement

A Appendix
Addr.
Parameter
2520
T 3I0> alarm
2530
WI non delayed
2531
WI delayed
2601
Operating Mode
2610
Iph>>
2611
T Iph>>
2612
3I0>> PICKUP
2613
T 3I0>>
2614
I>> Telep/BI
2615
I>> SOTF
2620
Iph>
2621
T Iph>
2622
3I0>
2623
T 3I0>
2624
I> Telep/BI
2625
I> SOTF
2630
Iph> STUB
2631
T Iph STUB
2632
3I0> STUB
2633
T 3I0 STUB
2634
I-STUB Telep/BI
2635
I-STUB SOTF
2640
Ip>
2642
T Ip Time Dial
2643
Time Dial TD Ip
2646
T Ip Add
2650
3I0p PICKUP
2652
T 3I0p TimeDial
2653
TimeDial TD3I0p
2656
T 3I0p Add
2660
IEC Curve
2661
ANSI Curve
536
Function
C
Setting Options
Weak Infeed
0.00 .. 30.00 sec
Weak Infeed
ON
OFF
Weak Infeed
ON
OFF
by receive fail
Back-Up O/C
ON:with VT loss
ON:always activ
OFF
0.10 .. 25.00 A; ∞
Back-Up O/C
1A
0.50 .. 125.00 A; ∞
5A
0.00 .. 30.00 sec; ∞
Back-Up O/C
0.05 .. 25.00 A; ∞
Back-Up O/C
1A
0.25 .. 125.00 A; ∞
5A
0.00 .. 30.00 sec; ∞
Back-Up O/C
Back-Up O/C
NO
YES
Back-Up O/C
NO
YES
0.10 .. 25.00 A; ∞
Back-Up O/C
1A
0.50 .. 125.00 A; ∞
5A
0.00 .. 30.00 sec; ∞
Back-Up O/C
0.05 .. 25.00 A; ∞
Back-Up O/C
1A
0.25 .. 125.00 A; ∞
5A
0.00 .. 30.00 sec; ∞
Back-Up O/C
Back-Up O/C
NO
YES
Back-Up O/C
NO
YES
0.10 .. 25.00 A; ∞
Back-Up O/C
1A
0.50 .. 125.00 A; ∞
5A
0.00 .. 30.00 sec; ∞
Back-Up O/C
0.05 .. 25.00 A; ∞
Back-Up O/C
1A
0.25 .. 125.00 A; ∞
5A
0.00 .. 30.00 sec; ∞
Back-Up O/C
Back-Up O/C
NO
YES
Back-Up O/C
NO
YES
0.10 .. 4.00 A; ∞
Back-Up O/C
1A
0.50 .. 20.00 A; ∞
5A
0.05 .. 3.00 sec; ∞
Back-Up O/C
0.50 .. 15.00 ; ∞
Back-Up O/C
Back-Up O/C
0.00 .. 30.00 sec
0.05 .. 4.00 A; ∞
Back-Up O/C
1A
0.25 .. 20.00 A; ∞
5A
0.05 .. 3.00 sec; ∞
Back-Up O/C
0.50 .. 15.00 ; ∞
Back-Up O/C
Back-Up O/C
0.00 .. 30.00 sec
Back-Up O/C
Normal Inverse
Very Inverse
Extremely Inv.
LongTimeInverse
Back-Up O/C
Inverse
Short Inverse
Long Inverse
Moderately Inv.
Very Inverse
Extremely Inv.
Definite Inv.
Default Setting
10.00 sec
3I0> exceeded delay for alarm
ON
WI non delayed
OFF
WI delayed
ON:with VT loss
Operating mode
2.00 A
Iph>> Pickup
10.00 A
0.30 sec
T Iph>> Time delay
0.50 A
3I0>> Pickup
2.50 A
2.00 sec
T 3I0>> Time delay
YES
Instantaneous trip via Teleprot./BI
NO
Instantaneous trip after Switch-
OnToFault
1.50 A
Iph> Pickup
7.50 A
0.50 sec
T Iph> Time delay
0.20 A
3I0> Pickup
1.00 A
2.00 sec
T 3I0> Time delay
NO
Instantaneous trip via Teleprot./BI
NO
Instantaneous trip after Switch-
OnToFault
1.50 A
Iph> STUB Pickup
7.50 A
0.30 sec
T Iph STUB Time delay
0.20 A
3I0> STUB Pickup
1.00 A
2.00 sec
T 3I0 STUB Time delay
NO
Instantaneous trip via Teleprot./BI
NO
Instantaneous trip after Switch-
OnToFault
∞ A
Ip> Pickup
∞ A
0.50 sec
T Ip Time Dial
5.00
Time Dial TD Ip
0.00 sec
T Ip Additional Time Delay
∞ A
3I0p Pickup
∞ A
0.50 sec
T 3I0p Time Dial
5.00
Time Dial TD 3I0p
0.00 sec
T 3I0p Additional Time Delay
Normal Inverse
IEC Curve
Inverse
ANSI Curve
Comments
7SA522 Manual
C53000-G1176-C155-3

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents