Siemens SIPROTEC 7SA522 Manual page 535

Distance protection
Hide thumbs Also See for SIPROTEC 7SA522:
Table of Contents

Advertisement

Addr.
Parameter
1451
Op. mode Z1B
1452
ZR(Z1B)
1471A
Mem.Polariz.PhE
1472A
CrossPolarizPhE
1473A
Mem.Polariz.P-P
1474A
CrossPolarizP-P
2002
P/S Op. mode
2006
PowerSwing trip
2007
Trip DELAY P/S
2101
FCT Telep. Dis.
2102
Type of Line
2103A
Send Prolong.
2107A
Delay for alarm
2108
Release Delay
2109A
TrBlk Wait Time
2110A
TrBlk BlockTime
2201
FCT Direct Trip
2202
Trip Time DELAY
2401
FCT SOTF-O/C
2404
I>>>
2501
FCT Weak Infeed
2502A
Trip/Echo DELAY
2503A
Trip EXTENSION
2504A
Echo BLOCK Time
2505
UNDERVOLTAGE
2509
Echo:1channel
2510
Uphe< Factor
Time const. τ
2511
2512A
Rec. Ext.
2513A
T 3I0> Ext.
2514
3I0> Threshold
2515
TM
2516
TT
2517
1pol. Trip
2518
1pol. with 3I0
2519
3pol. Trip
7SA522 Manual
C53000-G1176-C155-3
Function
C
Setting Options
Dis. MHO
Forward
Reverse
Inactive
0.050 .. 200.000 Ω
Dis. MHO
1A
0.010 .. 40.000 Ω
5A
Dis. MHO
0.0 .. 100.0 %
Dis. MHO
0.0 .. 100.0 %
Dis. MHO
0.0 .. 100.0 %
Dis. MHO
0.0 .. 100.0 %
Power Swing
All zones block
Z1/Z1B block
Z2 to Z5 block
Z1,Z1B,Z2 block
Power Swing
NO
YES
Power Swing
0.08 .. 5.00 sec; 0
Teleprot. Dist.
ON
PUTT (Z1B)
POTT
OFF
Teleprot. Dist.
Two Terminals
Three terminals
Teleprot. Dist.
0.00 .. 30.00 sec
Teleprot. Dist.
0.00 .. 30.00 sec
Teleprot. Dist.
0.000 .. 30.000 sec
0.00 .. 30.00 sec; ∞
Teleprot. Dist.
Teleprot. Dist.
0.00 .. 30.00 sec
DTT Direct Trip
ON
OFF
0.00 .. 30.00 sec; ∞
DTT Direct Trip
SOTF Overcurr.
ON
OFF
SOTF Overcurr.
1A
1.00 .. 25.00 A
5A
5.00 .. 125.00 A
Weak Infeed
OFF
ECHO only
ECHO and TRIP
Weak Infeed
0.00 .. 30.00 sec
Weak Infeed
0.00 .. 30.00 sec
Weak Infeed
0.00 .. 30.00 sec
Weak Infeed
2 .. 70 V
Weak Infeed
NO
YES
Weak Infeed
0.10 .. 1.00
Weak Infeed
1 .. 60 sec
Weak Infeed
0.00 .. 30.00 sec
Weak Infeed
0.00 .. 30.00 sec
Weak Infeed
1A
0.05 .. 1.00 A
5A
0.25 .. 5.00 A
Weak Infeed
0.00 .. 30.00 sec
Weak Infeed
0.00 .. 30.00 sec
Weak Infeed
ON
OFF
Weak Infeed
ON
OFF
Weak Infeed
ON
OFF
Default Setting
Forward
Operating mode Z1B (extended
zone)
3.000 Ω
ZR(Z1B), Impedance Reach
0.600 Ω
15.0 %
Voltagememory polarization
(phase-e)
15.0 %
Cross polarization (phase-e)
15.0 %
Voltagememory polarization
(phase-phase)
15.0 %
Cross polarization (phase-phase)
All zones block
Power Swing Operating mode
NO
Power swing trip
0.08 sec
Trip delay after Power Swing
Blocking
ON
Teleprotection for Distance prot. is
Two Terminals
Type of Line
0.05 sec
Time for send signal prolongation
10.00 sec
Time Delay for Alarm
0.000 sec
Time Delay for release after pickup
0.04 sec
Transient Block.: Duration external
flt.
0.05 sec
Transient Block.: Blk.T. after ext. flt.
OFF
Direct Transfer Trip (DTT)
0.01 sec
Trip Time Delay
ON
Inst. High Speed SOTF-O/C is
2.50 A
I>>> Pickup
12.50 A
ECHO only
Weak Infeed function is
0.04 sec
Trip / Echo Delay after carrier
receipt
0.05 sec
Trip Extension / Echo Impulse time
0.05 sec
Echo Block Time
25 V
Undervoltage (ph-e)
NO
Echo logic: Dis and EF on common
channel
0.70
Factor for undervoltage Uphe<
5 sec
Time constant Tau
0.65 sec
Reception extension
0.60 sec
3I0> exceeded extension
0.50 A
3I0 threshold for neutral current
pickup
2.50 A
0.40 sec
WI delay single pole
1.00 sec
WI delay multi pole
ON
Single pole WI trip allowed
ON
Single pole WI trip with 3I0
ON
Three pole WI trip allowed
A.7 Settings
Comments
535