Distance protection
Hide thumbs Also See for SIPROTEC 7SA522:
Table of Contents

Advertisement

Figure 2-97
Logic diagram of the high current switch on to fault protection

2.12.2 Setting Notes

Requirement
Pickup Threshold
2.12.3 Settings
Addr.
Parameter
2401
FCT SOTF-O/C
2404
I>>>
7SA522 Manual
C53000-G1176-C155-3
2.12 Instantaneous high-current switch-on-to-fault protection (SOTF)
A prerequisite for the operation of the switch-onto-fault protection is that in address
 627) 2YHUFXUU = (QDEOHG was set during the configuration of the device
scope of functions. At address  )&7 627)2& it can also be switched 21 or
2)).
The magnitude of the current which causes pick-up of the switch onto fault function is
set as ,!!! in address . The setting value should be selected large enough to
ensure that the protection under no circumstances picks up due to an overload condi-
tion or due to a current increase resulting from e.g. an automatic reclosure dead time
on a parallel feeder. It is recommended to set at least 2.5 times the rated current of the
feeder.
The table indicates region-specific presettings. Column C (configuration) indicates the
corresponding secondary nominal current of the current transformer.
C
Setting Options
ON
OFF
1A
1.00 .. 25.00 A
5A
5.00 .. 125.00 A
Default Setting
ON
Inst. High Speed SOTF-O/C
is
2.50 A
I>>> Pickup
12.50 A
Comments
225