2 Functions
212
Figure 2-95
Stub fault at an 1
If a short circuit current I
that a fault in the stub range between the current transformers I
lator exists. The circuit breakers CBA and CBC that carry the short-circuit current can
be tripped without delay. The two sets of current transformers are connected in parallel
such that the current sum I
tor.
The stub protection is an overcurrent protection which is only in service when the state
of the line isolator indicates the open condition via a binary input ´!,678%
(1$%/(µ. The binary input must therefore be operated via an auxiliary contact of the
isolator. In the case of a closed line isolator, the stub protection is out of service. For
more information see the next logic diagram.
If the stub protection stage is to be used as a normal definite time overcurrent stage,
the binary input ´!%/2&. ,678%µ, should be left without allocation or routing (ma-
trix). The enable input ´!,678% (1$%/(µ, however, has to be constantly activated
(either via a binary input or via integrated logic (CFC) functions which can be config-
ured by the user.
1
/
circuit breaker arrangement
2
and/or I
flows while the line isolator 1 is open, this implies
A
B
+ I
represents the current flowing towards the line isola-
A
B
, I
, and the line iso-
A
B