2 Functions
Pickup Logic and
Tripping Logic
214
The pickup signals of the individual phases (or the ground) and of the stages are linked
in such a way that both the phase information and the stage which has picked up are
output (Table 2-6).
Also for the tripping signals the element is indicated which has initiated the tripping. If
the device has the option to trip single-pole, and this option has been activated, the
pole which has been tripped is also indicated during single-pole tripping (refer also to
Subsection 2.20.1 "Tripping Logic of the Entire Device").
Table 2-6
Pickup signals of the individual phases
Internal Annunciation
I>> Pickup L1
I> Pickup L1
Ip Pickup L1
I>>> Pickup L1
I>> Pickup L2
I> Pickup L2
Ip Pickup L2
I>>> Pickup L2
I>> Pickup L3
I> Pickup L3
Ip Pickup L3
I>>> Pickup L1
I>> Pickup E
I> Pickup E
Ip Pickup E
I>>> Pickup E
I>> Pickup L1
I>> Pickup L2
I>> Pickup L3
I>> Pickup E
I> Pickup L1
I> Pickup L2
I> Pickup L3
I> Pickup E
Ip Pickup L1
Ip Pickup L2
Ip Pickup L3
Ip Pickup E
I>>> Pickup L1
I>>> Pickup L2
I>>> Pickup L3
I>>> Pickup E
(All pickups)
Figure
Output Annunciation
2-93
"O/C Pickup L1"
2-94
2-96
2-93
"O/C Pickup L2"
2-94
2-96
2-93
"O/C Pickup L3"
2-94
2-96
2-93
"O/C Pickup E"
2-94
2-96
2-93
2-93
"O/C PICKUP I>>"
2-93
2-93
"O/C PICKUP I>"
2-94
2-94
"O/C PICKUP Ip"
2-94
2-94
2-96
2-96
"I-STUB PICKUP"
2-96
2-96
"O/C PICKUP"
FNo.
7162
7163
7164
7165
7191
7192
7193
7201
7161
7SA522 Manual
C53000-G1176-C155-3