Siemens SIPROTEC 7SA522 Manual page 542

Distance protection
Hide thumbs Also See for SIPROTEC 7SA522:
Table of Contents

Advertisement

A Appendix
Addr.
Parameter
3510
Op.mode with AR
3511
Max. Volt. Diff
3512
Max. Freq. Diff
3513
Max. Angle Diff
3515A
SYNC-CHECK
3516
Usync> U-line<
3517
Usync< U-line>
3518
Usync< U-line<
3519
OVERRIDE
3530
Op.mode with MC
3531
MC maxVolt.Diff
3532
MC maxFreq.Diff
3533
MC maxAngleDiff
3535A
MC SYNCHR
3536
MC Usyn> Uline<
3537
MC Usyn< Uline>
3538
MC Usyn< Uline<
3539
MC O/RIDE
3601
O/U FREQ. f1
3602
f1 PICKUP
3603
f1 PICKUP
3604
T f1
3611
O/U FREQ. f2
3612
f2 PICKUP
3613
f2 PICKUP
3614
T f2
3621
O/U FREQ. f3
3622
f3 PICKUP
3623
f3 PICKUP
3624
T f3
3631
O/U FREQ. f4
3632
f4 PICKUP
3633
f4 PICKUP
3634
T f4
3701
Uph-e>(>)
3702
Uph-e>
3703
T Uph-e>
3704
Uph-e>>
3705
T Uph-e>>
3709A
Uph-e>(>) RESET
542
Function
C
Setting Options
Sync. Check
with T-CB close
w/o T-CB close
Sync. Check
1.0 .. 40.0 V
Sync. Check
0.03 .. 2.00 Hz
2 .. 80 °
Sync. Check
Sync. Check
YES
NO
Sync. Check
YES
NO
Sync. Check
YES
NO
Sync. Check
YES
NO
Sync. Check
YES
NO
Sync. Check
with T-CB close
w/o T-CB close
Sync. Check
1.0 .. 40.0 V
Sync. Check
0.03 .. 2.00 Hz
2 .. 80 °
Sync. Check
Sync. Check
YES
NO
Sync. Check
YES
NO
Sync. Check
YES
NO
Sync. Check
YES
NO
Sync. Check
YES
NO
Frequency Prot.
ON: Alarm only
ON: with Trip
OFF
Frequency Prot.
45.50 .. 54.50 Hz
Frequency Prot.
55.50 .. 64.50 Hz
Frequency Prot.
0.00 .. 600.00 sec
Frequency Prot.
ON: Alarm only
ON: with Trip
OFF
Frequency Prot.
45.50 .. 54.50 Hz
Frequency Prot.
55.50 .. 64.50 Hz
Frequency Prot.
0.00 .. 600.00 sec
Frequency Prot.
ON: Alarm only
ON: with Trip
OFF
Frequency Prot.
45.50 .. 54.50 Hz
Frequency Prot.
55.50 .. 64.50 Hz
Frequency Prot.
0.00 .. 600.00 sec
Frequency Prot.
ON: Alarm only
ON: with Trip
OFF
Frequency Prot.
45.50 .. 54.50 Hz
Frequency Prot.
55.50 .. 64.50 Hz
Frequency Prot.
0.00 .. 600.00 sec
Voltage Prot.
OFF
Alarm Only
ON
1.0 .. 170.0 V; ∞
Voltage Prot.
0.00 .. 100.00 sec; ∞
Voltage Prot.
1.0 .. 170.0 V; ∞
Voltage Prot.
0.00 .. 100.00 sec; ∞
Voltage Prot.
Voltage Prot.
0.30 .. 0.98
Default Setting
w/o T-CB close
Operating mode with AR
2.0 V
Maximum voltage difference
0.10 Hz
Maximum frequency difference
10 °
Maximum angle difference
YES
Live bus / live line and Sync before
AR
NO
Live bus / dead line check before
AR
NO
Dead bus / live line check before
AR
NO
Dead bus / dead line check before
AR
NO
Override of any check before AR
w/o T-CB close
Operating mode with Man.Cl
2.0 V
Maximum voltage difference
0.10 Hz
Maximum frequency difference
10 °
Maximum angle difference
YES
Live bus / live line and Sync before
MC
NO
Live bus / dead line check before
Man.Cl
NO
Dead bus / live line check before
Man.Cl
NO
Dead bus / dead line check before
Man.Cl
NO
Override of any check before
Man.Cl
ON: Alarm only
Over/Under Frequency Protection
stage f1
49.50 Hz
f1 Pickup
59.50 Hz
f1 Pickup
60.00 sec
T f1 Time Delay
ON: Alarm only
Over/Under Frequency Protection
stage f2
49.00 Hz
f2 Pickup
57.00 Hz
f2 Pickup
30.00 sec
T f2 Time Delay
ON: Alarm only
Over/Under Frequency Protection
stage f3
47.50 Hz
f3 Pickup
59.50 Hz
f3 Pickup
3.00 sec
T f3 Time Delay
ON: Alarm only
Over/Under Frequency Protection
stage f4
51.00 Hz
f4 Pickup
62.00 Hz
f4 Pickup
30.00 sec
T f4 Time Delay
OFF
Operating mode Uph-e overvolt-
age prot.
85.0 V
Uph-e> Pickup
2.00 sec
T Uph-e> Time Delay
100.0 V
Uph-e>> Pickup
1.00 sec
T Uph-e>> Time Delay
0.98
Uph-e>(>) Reset ratio
Comments
7SA522 Manual
C53000-G1176-C155-3