Basic Mode Configuration - Advantech ADAM-6217 User Manual

Adam-6200 series intelligent ethernet i/o module
Table of Contents

Advertisement

Basic Mode Configuration

The Status Display of basic mode is shown above. You can define the target device
by entering its IP address into the Destination text box in the Basic (One to One)
area.
You can choose these two methods by click the Deviation Enable check box (for AI
modules) or Enable Change of State check box (for digital modules). If this check box
is not checked, the transfer method is Period Time function. The period to transfer
data from source to destination is defined by the Period time numeric control in the
Basic (One to One) area. If the check box is checked, the transfer method becomes
Period Time function + C.O.S. function. You can define the deviation for analog input
by the Deviation Rate numeric control (value is percentage unit and represent the
change value divided by the total range). For Period Time function + C.O.S function,
the data will be transferred from source to destination periodically. Besides, when the
analog input value change is greater than what the Deviation Rate defined or the dig-
ital input channel value changes, the data will also update from source to destination
automatically.
By default, all input channels of the source module will all be mapping to all output
channels of the destination module. However, you can manually define which input
channels are mapping to output channels, by clicking the Modify channel enable
check box. When this check box is checked, you can select which input channels will
be mapping to the corresponding output channels by click related Channel check
box. In this example, only the value of input channels 0, 1, 2, 3 of the source module
will update to the output channels 0, 1, 2, 3 of the destination module. After you have
selected the channel, click the Apply list button to download this configuration to the
source module. You can save current mapping relation into a configuration file in your
computer by clicking the Save button. You also can load previous mapping configura-
tion file by clicking the Load button. If you click the Refresh button, the current map-
ping configuration on the source module will be displayed in the Channel-Enable
table.
ADAM-6200 User Manual
82

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Adam-6224Adam-6260Adam-6250Adam-6266Adam-6251Adam-6256

Table of Contents