Advantech ADAM-6217 User Manual page 168

Adam-6200 series intelligent ethernet i/o module
Table of Contents

Advertisement

$aaCjAh
Name
Description
Syntax
Response
Example
ASCII
ADAM-6200 User Manual
Read Alarm Mode
Returns the alarm mode for the specified channel in the specified
ADAM-6200 module.
$aaCjAh(cr)
$ is a delimiter character.
aa (range 00-FF) represents the 2-character hexadecimal slave
address of an ADAM-6200 module. (Always 01)
Cj identifies the desired channel j (j : 0 to 7).
A is the Read Alarm Mode command.
h indicates the alarm types (H = High alarm,
L = Low alarm)
(cr) represents terminating character, carriage return (0Dh)
!aas(cr) if the command was valid
?aa(cr) if an invalid operation was entered.
There is no response if the system detects a syntax error or communi-
cation error or if the address does not exist.
! delimiter indicating a valid command was received.
aa presents the 2-character hexadecimal slave address of the corre-
sponding ADAM-6200 module.
s indicates alarm modes (M = Momentary mode,
L = Latching mode)
(cr) represents terminating character, carriage return (0Dh)
Channel 1 of the ADAM-6200 module at address 01h is instructed to
return its Low alarm mode. The system responds that it is in Momen-
tary mode.
Command: $01C1AL(cr)
Response: !01M(cr)