Read Alarm Connection

Returns the High/Low alarm limit output connection of a specified input
channel in the addressed module
$aaCjRhC(cr)
$ is a delimiter character.
aa (range 00-FF) represents the 2-character hexadecimal slave
address of an ADAM-6200 module. (Always 01)
Cj identifies the desired analog input channel j (j : 0 to 7).
RhC is the Read Alarm Connection command.
h indicates alarm type (H = High alarm, L = Low alarm)
(cr) represents terminating character, carriage return (0Dh)
!aaCn(cr) if the command was valid
?aa(cr) if an invalid operation was entered.
There is no response if the system detects a syntax error or communi-
cation error or if the address does not exist.
! delimiter indicating a valid command was received.
aa represents the 2-character hexadecimal slave address of the corre-
sponding ADAM-6200 module.
Cn identifies the desired digital output channel n (n : 0 to 1) whether
interlock with the alarm of the specific analog input channel. If the val-
ues of n are "*", the analog input has no connection with a digital out-
put point.
(cr) represents terminating character, carriage return (0Dh)
Channel 1 of the ADAM-6200 module at address 01h is instructed to
read its Low alarm output connection. The system responds that the
Low alarm output connects to the digital output at channel 0 in the
specific module.
Command: $01C1RLC(cr)
Response:!01C0(cr)