Wiring & Connections; Power Supply Wiring; I/O Units - Advantech ADAM-6217 User Manual

Adam-6200 series intelligent ethernet i/o module
Table of Contents

Advertisement

3.3
Wiring & Connections
This section introduces basic information on wiring the power supply, I/O units, and
Ethernet connection.
3.3.1

Power Supply Wiring

The system of ADAM-6200 is designed for a standard industrial unregulated 24 V
power supply. For further application, it can also accept +10 to +30 V
input, 200mV peak to peak of power ripple, and the immediate ripple voltage should
be maintained between +10 and +30 V
Screw terminals +Vs and -Vs are for power supply wiring
Note!
The wires used should be at least 2 mm.
3.3.2

I/O Units

The system uses a plug-in screw terminal block for the interface between I/O mod-
ules and field devices. The following information must be considered when connect-
ing electrical devices to I/O modules.
1.
The terminal block accepts wires from 0.5 mm to 2.5 mm.
2.
Always use a continuous length of wire. Do not combine wires.
3.
Use the shortest possible wire length.
4.
Use wire trays for routing where possible.
5.
Avoid running wires near high-energy wiring.
6.
Avoid running input wiring in close proximity to output wiring.
7.
Avoid creating sharp bends in the wires.
.
DC
33
ADAM-6200 User Manual
DC
of power
DC

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Adam-6224Adam-6260Adam-6250Adam-6266Adam-6251Adam-6256

Table of Contents