B.1.3

Analog Input Range code

Range Code
+/- 10V
+/- 5 V
+/- 1 V
+/- 500 mV
+/- 150 mV
+/- 20 mA
0 ~ 20 mA
4 ~ 20 mA
Example
ASCII
B.1.4

Analog Input Alarm Command Set

Command Syntax Command Name
$aaCjAhs
$aaCjAh
$aaCjAhEs
$aaCjCh
$aaCjAhCCn
$aaCjRhC
$aaCjAhU
$aaCjRhU
$aaCjS
ADAM-6200 User Manual
HEX
0x0143
0x0142
0x0140
0x0104
0x0103
0x0181
0x0182
0x0180
The command asks the specific module at address 01h to send ana-
log input range code value from analog input channel 3.
Command: #01B03(cr)
Response: >010182(cr)
Set Alarm Mode
Read Alarm Mode
Enable/Dis-able Alarm
Clear Latch Alarm
Set Alarm Connection
Read Alarm Connection
Set Alarm Limit
Read Alarm Limit
Read Alarm Status
Description
Set the High/Low alarm in either Momentary or
Latch-ing mode
Returns the alarm mode for the specified chan-
nels
Enables/Disables the high/low alarm of the
specified channels
Resets a latched alarm
Connects the High/Low alarm of a specified
input channel to interlock with a specified out-
put channel
Returns the alarm configuration of a specified
input channel
Sets the High/Low alarm limit value to a speci-
fied channel
Returns the High/Low alarm limit value of the
speci-fied channel
Reads whether an alarm occurred in the speci-
fied channel