Local or Remote Internal Flag (AuxFlag)

You can assign the logic result value from the Execution stage, to local or remote
internal flag. Select the appropriate internal flag by the Index combo box. Define what
value you want to assign to the internal flag for the true action (When the logic result
value passed from Execution stage is logic True) by the True Action combo box. The
false action (When the logic result value is logic False) is displayed by the False
Action text box and will automatically be opposite to the value in the True Action.
After you have completed the setting, click the OK button.

Remote Message Output (RemoteMessage)

We can send the Device Description (you can edit it by the Message text box in the
Operation area) as message to the target device. When you have several logic rules
which all will send message, we need to know the message received by the target
device is sent by which logic rule. So, you can give the message a index, defined by
the Value text box in the Operation area. Click OK to complete the configuration. So
when logic result value passed from the Execution stage is true, the message will be
sent to the target device. If the logic result is False, the message won't be sent out.

Local Internal Counter Setting (Counter)

Below are the steps to configure internal counter setting:
1.
Define what action (increase one count to internal counter value by Positive
edge trigger (F->T), or reset internal counter by Reset) will be taken for the true
action (When the logic result value passed from Execution stage is logic True)
by the True Action combo box.
Note!
When you choose Positive edge trigger (F->T) as action, the counter will
only add one count for the first time that the logic result value from Exe-
cution Stage is logic high. After the first time, the counter value will not
change even the logic result value from Execution Stage is still logic
high. So it is the reason why it is called positive edge trigger.
2.
The false action (When the logic result value passed from Execution stage is
logic False) is displayed by the False Action text box and will automatically be
set according to the true action. The false action will be opposite to the true
action. Refer to the table below to see the relationship between true action and
false action.
3.
Define which counter channel is responsible to take the defined action by the
Channel combo box.
4.
Click the OK button to complete the configuration.