Read AO Startup Value from One Channel

Returns the startup value from a specified analog output channel in a
specified module.
$aaDScc(cr)
$ is a delimiter character.
aa (range 00-FF) represents the 2-character hexadecimal slave
address of the ADAM-6200 module you want to request. (Always 01)
DS represents the analog output channel startup command.
cc (range 00-01) represents the specific channel you want to read the
startup value.
(cr) is the terminating character, carriage return (0Dh).
!aannnn(cr) if the command is valid.
?aa(cr) if an invalid operation was entered.
There is no response if the module detects a syntax error or communi-
cation error or if the address does not exist.
! delimiter indicating a valid command was received.
? delimiter indicating the command was invalid.
aa (range 00-FF) represents the 2-character hexadecimal slave
address of the ADAM-6200 module you want to request. (Always 01)
nnnn (range: 0000-0FFF) represents the 4-character hexadecimal
startup value of the specific AO channel.
(cr) is the terminating character, carriage return (0Dh).
Startup value for analog output channel 1 of the ADAM-6224 module
at address 01h responds with a value +10.000. (The AO range of
channel 1 is 0~10V)
Command: $01DS01(cr)