Read Alarm Limit

Returns the High/Low alarm limit value for the specified input channel
in the addressed ADAM-6200 module
$aaCjRhU(cr)
$ is a delimiter character.
aa (range 00-FF) represents the 2-character hexadecimal slave
address of an ADAM-6200 module.(Always 01)
Cj identifies the desired analog input channel j (j : 0 to 7).
RhU is the Read Alarm Limit command.
h indicates alarm type (H = High alarm, L = Low alarm)
(cr) represents terminating character, carriage return (0Dh)
!aa(data)(cr) if the command was valid
?aa(cr) if an invalid operation was entered.
There is no response if the system detects a syntax error or communi-
cation error or if the address does not exist.
! delimiter indicating a valid command was received.
aa represents the 2-character hexadecimal slave address of the corre-
sponding ADAM-6200 module.
(data) represents the desired alarm limit setting. The format is always
in engineering units.
(cr) represents terminating character, carriage return (0Dh)
Channel 1 of the ADAM-6200 module at address 01h is configured to
accept 5V input. The command instructs the system to return the High
alarm limit value for that channel. The system responds that the High
alarm limit value in the desired channel is 2.0500 V.
Command: $01C1RHU(cr)
Response: !01+2.0500(cr)