2.3
Analog Output Module (ADAM-6224)
Analog Output
Channel
Voltage Output Range
Current Output Range
Driving Load
Output Impedance
Accuracy
Resolution
Output settling Time
Programmable Output
Slope
Other Functions
Digital Input
Channel
Dry Contact
Other Functions
2.3.1
Application Wiring
Description
4
±5 V, ±10 V, 0~5 V, 0~10 V
0 ~ 20 mA, 4 ~ 20 mA
Voltage: Min. 2kΩ
Current: Max. 500 Ω
2.1 Ω
0.3% of FSR (Voltage) at 25°C
0.5% of FSR (Current) at 25°C
12-bit
20 μs
0.125 – 128 mA/sec
0.0625 – 64 V/sec
Independent Channel Range Type
Current Output Open-wired Detect Function
Startup Value Setting
Communication Safety Value Setting
Digital Input Trigger Analog Output Function
Description
4
Logic 0: Open
Logic 1: Closed to Iso.GND
Support DI Filter
Support Inverted DI Status
Support Trigger to Startup or Safety Value
17