Pilot Schemes - GE D60 Instruction Manual

Line distance protection system
Hide thumbs Also See for D60:
Table of Contents

Advertisement

CONTROL ELEMENTS

5.8.14 Pilot schemes

SETTINGS  CONTROL ELEMENTS  PILOT SCHEMES
 PILOT SCHEMES
5.8.14.1 Direct under-reaching transfer trip (DUTT)
SETTINGS  CONTROL ELEMENTS  PILOT SCHEMES  DUTT SCHEME
5
 DUTT SCHEME
This scheme uses an under-reaching Zone 1 distance element to key a transfer trip signal(s) to the remote end(s), where on
receipt, the DUTT pilot scheme operates without additional protection supervision. For proper operation of the scheme, the
Zone 1 phase and ground distance elements must be enabled, configured, and set per rules of distance relaying.
In single-pole tripping applications, the scheme uses local fault type identification provided by the Phase Selector together
with information received from the remote terminal(s). The latter can be coded into one, two, or four bits over the
communications channel.
5-350
 DUTT SCHEME
 PUTT SCHEME
 POTT SCHEME
 POTT1 SCHEME
 HYBRID POTT SCHEME
 BLOCKING SCHEME
 BLOCKING1 SCHEME
 DCUB SCHEME
DUTT SCHEME
FUNCTION: Disabled
DUTT SCHEME BLOCK:
Off
DUTT SEAL-IN
DELAY: 0.010 s
DUTT NO OF COMM
BITS: 1
DUTT RX1:
Off
DUTT RX2:
Off
DUTT RX3:
Off
DUTT RX4:
Off
DUTT SCHEME TARGET:
Self-Reset
DUTT SCHEME EVENT:
Disabled
See below
See page 5-352
See page 5-354
See page 5-357
See page 5-358
See page 5-362
See page 5-366
See page 5-368
Range: Disabled, Enabled
Range: FlexLogic operand
Range: 0.000 to 65.535 s in steps of 0.001
Range: 1, 2, or 4
Range: FlexLogic operand
Range: FlexLogic operand
Range: FlexLogic operand
Range: FlexLogic operand
Range: Self-Reset, Latched, Disabled
Range: Disabled, Enabled
D60 LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
CHAPTER 5: SETTINGS

Advertisement

Table of Contents
loading

Table of Contents