GE D60 Instruction Manual page 530

Line distance protection system
Hide thumbs Also See for D60:
Table of Contents

Advertisement

CONTROL ELEMENTS
5
5.8.14.2 Permissive under-reaching transfer trip (PUTT)
SETTINGS  CONTROL ELEMENTS  PILOT SCHEMES  PUTT SCHEME
 PUTT SCHEME
5-352
Figure 5-203: DUTT scheme logic
PUTT SCHEME
FUNCTION: Disabled
PUTT SCHEME BLOCK:
Off
PUTT RX PICKUP
DELAY: 0.000 s
PUTT SEAL-IN
DELAY: 0.010 s
PUTT NO OF COMM
BITS: 1
PUTT RX1:
Off
PUTT RX2:
Off
Range: Disabled, Enabled
Range: FlexLogic operand
Range: 0.000 to 65.535 s in steps of 0.001
Range: 0.000 to 65.535 s in steps of 0.001
Range: 1, 2, or 4
Range: FlexLogic operand
Range: FlexLogic operand
D60 LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
CHAPTER 5: SETTINGS