CONTROL ELEMENTS
5
5.8.14.3 Permissive overreaching transfer trip (POTT)
SETTINGS  CONTROL ELEMENTS  PILOT SCHEMES  POTT SCHEME
 POTT SCHEME
5-354
Figure 5-204: PUTT scheme logic
POTT SCHEME
FUNCTION: Disabled
POTT PERMISSIVE
ECHO: Disabled
POTT RX PICKUP
DELAY: 0.000 s
TRANS BLOCK PICKUP
DELAY: 0.020 s
TRANS BLOCK RESET
DELAY: 0.090 s
ECHO DURATION:
0.100 s
ECHO LOCKOUT:
0.250 s
LINE END OPEN PICKUP
DELAY: 0.050 s
POTT SEAL-IN
DELAY: 0.400 s
Range: Disabled, Enabled
Range: Disabled, Enabled
Range: 0.000 to 65.535 s in steps of 0.001
Range: 0.000 to 65.535 s in steps of 0.001
Range: 0.000 to 65.535 s in steps of 0.001
Range: 0.000 to 65.535 s in steps of 0.001
Range: 0.000 to 65.535 s in steps of 0.001
Range: 0.000 to 65.535 s in steps of 0.001
Range: 0.000 to 65.535 s in steps of 0.001