GE D60 Instruction Manual page 548

Line distance protection system
Hide thumbs Also See for D60:
Table of Contents

Advertisement

CONTROL ELEMENTS
Coordinate the selected protection element (or elements in combination) with the selection of
forward external faults seen by an element set as
as
GND DIR O/C REV
directional element operation during transients, adding at least 0.5 cycles of pickup delay to the forward directional
element is recommended.
— This setting defines the FlexLogic operand (if any) of a protection element used in addition to zone 4 for
GND DIR O/C REV
identifying reverse faults, and thus, for stopping the transmit signal and initiating the transient blocking timer.
Good directional integrity is the key requirement for a reverse-looking protection element set as
though any FlexLogic operand can be set as
protection elements or to apply extra conditions through FlexLogic equations, this extra signal is primarily meant to be the
output operand from either the negative-sequence directional or neutral directional overcurrent element. As both these
elements have separate forward and reverse output operands, use the reverse indication (that is,
NEUTRAL DIR OC1
REV).
Coordinate the selected protection element (or elements in combination) with the selection of
forward external faults seen by an element set as
as
GND DIR O/C REV
directional element operation during transients, adding a pickup delay greater than the pilot channel delay to the reverse
directional element is recommended.
TRANS BLOCK PICKUP DELAY
unblocking scheme for coping with the exposure of both the over-reaching zone 2 and ground directional overcurrent
function to current reversal conditions.
The transient blocking logic applies to both operate (trip) and send (transmit) paths. Identifying the fault as a reverse fault
prevents the scheme from both operating and keying the channel. If the reverse fault condition prevails for
value, the blocking operation is extended by the transient blocking timer for the
5
PICKUP DELAY
value. This allows riding through current reversal conditions.
However, if distance zone 1 picks up during the transient blocking condition, the blocking action is removed. This is to cope
with evolving faults when an external fault is followed by an internal fault. Without the zone 1 feedback, the trip is delayed
unnecessarily.
Do not set the
TRANS BLOCK PICKUP DELAY
extended blocking action can be established. Take into account the pickup time of the reverse-looking elements of the
scheme. To avoid locking up a spurious reverse fault indication that can occur during internal fault conditions, do not set
the delay defined by this setting too short.
TRANS BLOCK RESET DELAY
unblocking scheme for coping with the exposure of the overreaching protection functions to current reversal conditions
(see also the previous
Set this delay long enough to cope with transient conditions including not only current reversals but also spurious negative
and zero-sequence currents occurring during breaker operations (in the case when neutral directional or negative-
sequence directional overcurrent functions are used). Consider the breaker failure time of the surrounding protection
systems within the reach of the ground directional function used by the directional comparison unblocking scheme, to
make sure that the ground directional function is not jeopardized during delayed breaker operations.
— This setting defines the guaranteed and exact duration of the echo pulse. The duration does not depend
ECHO DURATION
on the duration and shape of the received
transmit/receive loop.
— This setting defines the lockout period for the echo logic after sending the echo pulse. This setting
ECHO LOCKOUT
enables the relay to avoid oscillations of the echo pulses during an autoreclosure dead-time after clearing an internal
fault.
LINE END OPEN PICKUP DELAY
detected by the line pickup logic via the
requirement for the directional comparison unblocking scheme to return a received echo signal (if the echo feature is
enabled).
When selecting this delay value, take into account the principle of operation and settings of the line pickup element, which
should thus be enabled.
5-370
at the other end picks up and provides a blocking signal. For greater security and to overcome spurious
GND DIR O/C REV
at the other end picks up and provides a blocking signal. For greater security and to overcome spurious
— This setting defines a transient blocking mechanism embedded in the directional comparison
longer than the fastest possible trip time for faults on an adjacent line so that
— This setting defines a transient blocking mechanism embedded in the directional comparison
TRANS BLOCK PICKUP DELAY
signals. This setting enables the relay to avoid a permanent lock-up of the
RX
— This setting defines the pickup value for validation of the line end open conditions as
LINE PICKUP LEO PKP
at one end of the line, the reverse-looking element set
GND DIR O/C FWD
, thereby enabling the user to combine responses of various
at one end of the line, the reverse-looking element set
GND DIR O/C FWD
setting).
FlexLogic operand. The validated line end open condition is a
D60 LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
CHAPTER 5: SETTINGS
. For all
GND DIR O/C REV
. Even
GND DIR O/C REV
or
NEG SEQ DIR OC1 REV
. For all the
GND DIR O/C FWD
TRANS BLOCK
TRANS BLOCK RESET DELAY

Advertisement

Table of Contents
loading

Table of Contents