CHAPTER 5: SETTINGS
Transient Fault — When the first reclose output signal is sent to close Breaker 1, the reset timer starts. The close
Breaker 1 signal initiates the transfer timer that times out and sends the close signal to the second breaker. If the
reclosure sequence is successful (both breakers closed and there is no initiating signal), the reset timer times out,
returning the scheme to the reset state with the shot counter set to 0. The scheme is ready for a new reclose cycle.
AR BKR1(2) reclose fail
If the selected sequence is "1–2" or "2–1" and after the first or second reclose attempt the breaker fails to close, there are
two options. If the
AR BKR 1(2) FAIL OPTION
the reclose process continues with Breaker 2. At the same time the shot counter is decreased (since the closing process
was not completed).
Scheme reset after reclosure
When a reclose output signal is sent to close either breaker 1 or 2, the reset timer is started. If the reclosure sequence is
successful (there is no initiating signal and the breakers are closed), the reset timer times out, returning the scheme to the
reset state, with the shot counter set to 0, making it ready for a new reclose cycle.
In two breaker schemes, if one breaker is in the out-of-service state and the other is closed at the end of the reset time, the
scheme also resets. If at the end of the reset time at least one breaker, which is not in the out-of-service state, is open the
scheme is sent to Lockout.
The reset timer is stopped if the reclosure sequence is not successful: an initiating signal present or the scheme is in
Lockout state. The reset timer is also stopped if the breaker is manually closed or the scheme is otherwise reset from
lockout.
Lockout
When a reclose sequence starts by an initiate signal, the scheme moves into the reclose-in-progress state and starts the
incomplete sequence timer. The setting of this timer determines the maximum time interval allowed for a single reclose
shot. If a close breaker 1 or 2 signal is not present before this time expires, the scheme goes to "Lockout".
There are four other conditions that can take the scheme to the Lockout state, as follows:
Receipt of 'Block' input while in the reclose-in-progress state
The reclosing program logic — When a 3P Initiate is present and the autoreclose mode is either 1 Pole or 3Pole-A (3
pole autoreclose for single pole faults only)
Initiation of the scheme when the count is at the maximum allowed
If at the end of the reset time at least one breaker, which is not in the out-of-service state, is open the scheme is sent
to Lockout. The scheme is also sent to Lockout if one breaker fails to reclose and the setting
to "Lockout".
Once the Lockout state is set, it is latched until one or more of the following occurs:
The scheme is intentionally reset from Lockout, employing the Reset setting of the Autorecloser
The Breaker(s) is(are) manually closed from panel switch, SCADA, or other remote control through the
setting;
CLOSE
10 seconds after breaker control detects that breaker(s) were closed
Breaker open before fault
A logic circuit is provided that inhibits the close breaker 1 and close breaker 2 outputs if a reclose initiate (RIP) indicator is
not present within 30 ms of the Breaker Any Phase Open input. This feature is intended to prevent reclosing if one of the
breakers was open in advance of a reclose initiate input to the recloser. This logic circuit resets when the breaker is closed.
Transfer reclose when breaker is blocked
When the reclosing sequence 1-2 is selected and Breaker 1 is blocked
can be transferred direct to the Breaker 2 if
Lockout by the incomplete sequence timer.
D60 LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
is set to "Lockout," the scheme goes to lockout state. When it is set to "Continue,"
is set to "Yes." If set to "No", the scheme is sent to
AR TRANSFER 1 TO 2
CONTROL ELEMENTS
AR BKR FAIL OPTION
(AR BKR1 BLK
operand is set) the reclose signal
5
is set
AR BRK MAN
5-311