GE D60 Instruction Manual page 540

Line distance protection system
Hide thumbs Also See for D60:
Table of Contents

Advertisement

CONTROL ELEMENTS
5
5.8.14.6 Directional comparison blocking
SETTINGS  CONTROL ELEMENTS  PILOT SCHEMES  BLOCKING SCHEME
 BLOCKING SCHEME
5-362
Figure 5-207: Hybrid POTT scheme logic
BLOCKING SCHEME
FUNCTION: Disabled
BLOCK SCHEME BLOCK:
Off
BLOCK RX CO-ORD PKP
DELAY: 0.010 s
Range: Disabled, Enabled
Range: FlexLogic operand
Range: 0.000 to 65.535 s in steps of 0.001
D60 LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
CHAPTER 5: SETTINGS