CHAPTER 5: SETTINGS
I
is the measured overload RMS current at index n
n
E
is the accumulated energy at index n
n
E
is the accumulated energy at index n – 1
n – 1
The thermal overload protection element removes the
emergency, the thermal memory and
All calculations are performed per phase. If the accumulated energy reaches value 1 in any phase, the thermal overload
protection element operates and only resets when energy is less than 0.05 in all three phases.
Table 5-43: Typical time constants
Protected equipment
Capacitor bank
Overhead line
Air-core reactor
Busbar
Underground cable
The figure shows the logic for the thermal overload protection element.
5.8.13.10 Broken conductor detection
SETTINGS  CONTROL ELEMENTS  MONITORING ELEMENTS  BROKEN CONDUCTOR 1(2)
 BROKEN CONDUCTOR 1
D60 LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
THERMAL PROT 1 OP
output operand can be reset using
THERMAL PROT 1 OP
Time constant
Minimum reset time
10 minutes
30 minutes
10 minutes
20 minutes
40 minutes
30 minutes
60 minutes
20 minutes
20 to 60 minutes
60 minutes
Figure 5-201: Thermal overload protection logic
BROKEN CONDUCTOR 1
FUNCTION: Disabled
BROKEN CONDUCTOR 1
SOURCE: SRC 1
BROKEN CONDUCTOR 1
I2/I1 RATIO: 20%
BROKEN CONDUCTOR 1
I1 MIN: 0.10 pu
output operand when E < 0.05. In case of
THERM PROT 1 RESET
Range: Disabled, Enabled
Range: SRC 1, SRC 2, SRC 3, SRC 4
Range: 20.0% to 100.0% in steps of 0.1%
Range: 0.05 to 1.00 pu in steps of 0.01
CONTROL ELEMENTS
setting.