CONTROL ELEMENTS
5
5.8.5 Trip output
SETTINGS CONTROL ELEMENTS TRIP OUTPUT
TRIP OUTPUT
5-292
Figure 5-170: Selector switch logic
TRIP MODE:
Disabled
TRIP 3-POLE INPUT1:
Off
TRIP 3-POLE INPUT6:
Off
TRIP 1-POLE INPUT1:
Off
TRIP 1-POLE INPUT6:
Off
TRIP RECLOSE INPUT1:
Off
TRIP RECLOSE INPUT6:
Off
TRIP SEAL-IN DELAY:
0.000 s
Range: Disabled, 3 Pole Only, 3 Pole & 1 Pole
Range: FlexLogic operand
Range: FlexLogic operand
Range: FlexLogic operand
Range: FlexLogic operand
Range: FlexLogic operand
Range: FlexLogic operand
Range: 0 to 65.535 s in steps of 0.001
D60 LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
CHAPTER 5: SETTINGS