GE D60 Instruction Manual page 514

Line distance protection system
Hide thumbs Also See for D60:
Table of Contents

Advertisement

CONTROL ELEMENTS
BRK RSTR 1 BRK OPEN
the breaker is open. It is important to assign either 52 contact with this setting or breaker close command with
setting to give clear indication to the relay about breaker status.
CLS CMD
BRK RSTR 1 OPEN CMD
breaker is opened, either manually or from protection logic.
BRK RSTR 1 CLS CMD
breaker is closed.
5
5.8.13.5 CT failure detector
SETTINGS  CONTROL ELEMENTS  MONITORING ELEMENTS  CT FAILURE DETECTOR 1(4)
 CT FAILURE
 DETECTOR 1
5-336
— Assigns a FlexLogic operand indicating the open position of the breaker. It must be logic "1" when
— Assigns a FlexLogic operand indicating a breaker open command. It must be logic "1" when the
— Assigns a FlexLogic operand indicating a breaker close command. It must be logic "1" when the
Figure 5-193: Breaker restrike logic
CT FAIL 1 FUNCTION:
Disabled
CT FAIL 1 BLOCK:
Off
CT FAIL 1 3I0 INP 1:
SRC 1
CT FAIL 1 3I0 INP 1
PKP: 0.2 pu
CT FAIL 1 3I0 INP 2:
SRC 2
CT FAIL 1 3I0 INP 2
PKP: 0.2 pu
CT FAIL 1 3V0 INPUT:
SRC 1
CT FAIL 1 3V0 INPUT
PKP: 0.20 pu
CT FAIL 1 PICKUP
DELAY: 1.000 s
CT FAIL 1 TARGET:
Self-reset
Range: Disabled, Enabled
Range: FlexLogic operand
Range: SRC 1, SRC 2, SRC 3, SRC 4
Range: 0.1 to 2.0 pu in steps of 0.1
Range: SRC 1, SRC 2, SRC 3, SRC 4
Range: 0.1 to 2.0 pu in steps of 0.1
Range: SRC 1, SRC 2, SRC 3, SRC 4
Range: 0.04 to 2.00 pu in steps of 0.01
Range: 0.000 to 65.535 s in steps of 0.001
Range: Self-reset, Latched, Disabled
D60 LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
CHAPTER 5: SETTINGS
BRK RSTR 1