GE D60 Instruction Manual page 384

Line distance protection system
Hide thumbs Also See for D60:
Table of Contents

Advertisement

GROUPED ELEMENTS
5
For phase distance zone 2, there is a provision to start the zone timer with other distance zones or loop the pickup
flag to avoid prolonging phase distance zone 2 operation when the fault evolves from one type to another or
migrates from the initial zone to zone 2. Assign the required zones in the trip output function to accomplish this
functionality.
5-206
Figure 5-108: Phase distance zone 1 OP logic
Figure 5-109: Phase distance zone 2 OP logic
D60 LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
CHAPTER 5: SETTINGS

Advertisement

Table of Contents
loading

Table of Contents