GE D60 Instruction Manual page 633

Line distance protection system
Hide thumbs Also See for D60:
Table of Contents

Advertisement

CHAPTER 8: APPLICATION OF SETTINGS
The Zone 1 settings are:
: "0.80"
PHS DIST Z1 REACH
: "85"
PHS DIST Z1 RCA
PHS DIST Z1 XMFR VOL CONNECTION
PHS DIST Z1 XMFR CUR CONNECTION
The Zone 4 settings are:
: "2.60"
PHS DIST Z4 REACH
: "89"
PHS DIST Z4 RCA
PHS DIST Z4 XMFR VOL CONNECTION
PHS DIST Z4 XMFR CUR CONNECTION
D60 LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
: "None"
: "Dy1"
: "Yd11"
: "None"
PHASE DISTANCE THROUGH POWER TRANSFORMERS
Eq. 8-9
Eq. 8-10