Pilot Schemes - GE D60 Instruction Manual

Ur series line distance protection system
Hide thumbs Also See for D60:
Table of Contents

Advertisement

5.7 CONTROL ELEMENTS
a) MAIN MENU

PATH: SETTINGS
CONTROL ELEMENTS
 PILOT SCHEMES
5
This menu allows selecting and configuring protection signaling schemes. All schemes are available for single-pole tripping
applications and can be used with one, two, or four-bit communications channels. Choices of communications channel
include Remote Inputs/Outputs and telecommunications interfaces.
For more information, see the Theory of Operation and Application of Settings chapters
b) DIRECT UNDER-REACHING TRANSFER TRIP (DUTT)

PATH: SETTINGS
CONTROL ELEMENTS
 DUTT SCHEME
5-320


PILOT SCHEMES

 DUTT SCHEME
 PUTT SCHEME
MESSAGE
 POTT SCHEME
MESSAGE
 POTT1 SCHEME
MESSAGE
 HYBRID POTT SCHEME
MESSAGE
 BLOCKING SCHEME
MESSAGE
 BLOCKING1 SCHEME
MESSAGE
 DCUB SCHEME
MESSAGE

PILOT SCHEMES
DUTT SCHEME
FUNCTION: Disabled
DUTT SCHEME BLOCK:
MESSAGE
Off
DUTT SEAL-IN
MESSAGE
DELAY: 0.010 s
DUTT NO OF COMM
MESSAGE
BITS: 1
DUTT RX1:
MESSAGE
Off
DUTT RX2:
MESSAGE
Off
DUTT RX3:
MESSAGE
Off
DUTT RX4:
MESSAGE
Off
DUTT SCHEME TARGET:
MESSAGE
Self-Reset
D60 Line Distance Protection System
See page 5–320.
See page 5–323.
See page 5–325.
See page 5–329.
See page 5–331.
See page 5–335.
See page 5–339.
See page 5–341.
DUTT SCHEME
Range: Disabled, Enabled
Range: FlexLogic operand
Range: 0.000 to 65.535 s in steps of 0.001
Range: 1, 2, or 4
Range: FlexLogic operand
Range: FlexLogic operand
Range: FlexLogic operand
Range: FlexLogic operand
Range: Self-Reset, Latched, Disabled
5 SETTINGS
5.7.14 PILOT SCHEMES
GE Multilin

Advertisement

Table of Contents
loading

Table of Contents