5.7 CONTROL ELEMENTS
a) MAIN MENU
PATH: SETTINGS
CONTROL ELEMENTS
PILOT SCHEMES
This menu contains settings for selecting and configuring protection signaling schemes. All schemes are available for sin-
gle-pole tripping applications and can be used with one, two, or four-bit communications channels. Choices of communica-
5
tions channels include remote inputs/outputs and telecommunications interfaces.
b) DIRECT UNDER-REACHING TRANSFER TRIP (DUTT)
PATH: SETTINGS
CONTROL ELEMENTS
DUTT SCHEME
5-302
PILOT SCHEMES
DUTT SCHEME
PUTT SCHEME
MESSAGE
POTT SCHEME
MESSAGE
POTT1 SCHEME
MESSAGE
HYBRID POTT SCHEME
MESSAGE
BLOCKING SCHEME
MESSAGE
DCUB SCHEME
MESSAGE
PILOT SCHEMES
DUTT SCHEME
FUNCTION: Disabled
DUTT SCHEME BLOCK:
MESSAGE
Off
DUTT SEAL-IN
MESSAGE
DELAY: 0.010 s
DUTT NO OF COMM
MESSAGE
BITS: 1
DUTT RX1:
MESSAGE
Off
DUTT RX2:
MESSAGE
Off
DUTT RX3:
MESSAGE
Off
DUTT RX4:
MESSAGE
Off
DUTT SCHEME TARGET:
MESSAGE
Self-Reset
DUTT SCHEME EVENTS:
MESSAGE
Disabled
D60 Line Distance Protection System
See page 5–302.
See page 5–305.
See page 5–307.
See page 5–311.
See page 5–313.
See page 5–317.
See page 5–321.
DUTT SCHEME
Range: Disabled, Enabled
Range: FlexLogic operand
Range: 0.000 to 65.535 s in steps of 0.001
Range: 1, 2, or 4
Range: FlexLogic operand
Range: FlexLogic operand
Range: FlexLogic operand
Range: FlexLogic operand
Range: Self-Reset, Latched, Disabled
Range: Disabled, Enabled
5 SETTINGS
5.7.14 PILOT SCHEMES
GE Multilin