5.7 CONTROL ELEMENTS
a) MAIN MENU

PATH: SETTINGS
CONTROL ELEMENTS
 PILOT SCHEMES
This menu contains settings for selecting and configuring protection signaling schemes. All schemes are available for sin-
gle-pole tripping applications and can be used with one, two, or four-bit communications channels. Choices of communica-
5
tions channels include remote inputs/outputs and telecommunications interfaces.
b) DIRECT UNDER-REACHING TRANSFER TRIP (DUTT)

PATH: SETTINGS
CONTROL ELEMENTS
 DUTT SCHEME
5-302


PILOT SCHEMES

 DUTT SCHEME
 PUTT SCHEME
MESSAGE
 POTT SCHEME
MESSAGE
 POTT1 SCHEME
MESSAGE
 HYBRID POTT SCHEME
MESSAGE
 BLOCKING SCHEME
MESSAGE
 DCUB SCHEME
MESSAGE

PILOT SCHEMES
DUTT SCHEME
FUNCTION: Disabled
DUTT SCHEME BLOCK:
MESSAGE
Off
DUTT SEAL-IN
MESSAGE
DELAY: 0.010 s
DUTT NO OF COMM
MESSAGE
BITS: 1
DUTT RX1:
MESSAGE
Off
DUTT RX2:
MESSAGE
Off
DUTT RX3:
MESSAGE
Off
DUTT RX4:
MESSAGE
Off
DUTT SCHEME TARGET:
MESSAGE
Self-Reset
DUTT SCHEME EVENTS:
MESSAGE
Disabled
D60 Line Distance Protection System
See page 5–302.
See page 5–305.
See page 5–307.
See page 5–311.
See page 5–313.
See page 5–317.
See page 5–321.
DUTT SCHEME
Range: Disabled, Enabled
Range: FlexLogic operand
Range: 0.000 to 65.535 s in steps of 0.001
Range: 1, 2, or 4
Range: FlexLogic operand
Range: FlexLogic operand
Range: FlexLogic operand
Range: FlexLogic operand
Range: Self-Reset, Latched, Disabled
Range: Disabled, Enabled