GE D60 Instruction Manual page 372

Line distance protection system
Hide thumbs Also See for D60:
Table of Contents

Advertisement

GROUPED ELEMENTS
The line pickup feature uses a combination of undercurrent and undervoltage to identify a line that has been de-energized
(line end open). Alternately assign a FlexLogic operand to the
5
Three instantaneous overcurrent elements are used to identify a previously de-energized line that has been closed onto a
fault. Faults other than close-in faults can be identified satisfactorily with the distance elements.
Co-ordination features are included to ensure satisfactory operation when high-speed automatic reclosure (AR) is
employed. The
AR CO-ORD DELAY
reclose. Co-ordination is achieved by all of the
times out. The
CO-ORD DELAY
implemented.
The line pickup protection incorporates zone 1 extension capability. When the line is being re-energized from the local
terminal, pickup of an overreaching zone 2 or excessive phase current within eight power cycles after the autorecloser
issues a close command results in the
supervised by an undervoltage condition, which in turn is controlled by the
coordination timer. If a trip from distance is not required, then it can be disabled with the
Configure the
LINE PICKUP RCL TRIP
The zone 1 extension philosophy used here normally operates from an under-reaching zone, and it uses an overreaching
distance zone when reclosing the line with the other line end open. The
1 extension functionality if external autoreclosure is employed. Another zone 1 extension approach is to apply
permanently an overreaching zone, and reduce the reach when reclosing. This philosophy can be programmed via the
autoreclose scheme.
LINE PICKUP FUNCTION
LINE PICKUP SIGNAL SOURCE
PHASE IOC LINE PICKUP
energized.
LINE END OPEN PICKUP DELAY
armed.
LINE END OPEN RESET DELAY
re-energized.
5-194
LINE PICKUP OV PKP
DELAY: 0.040 s
AR CO-ORD BYPASS:
Enabled
AR CO-ORD PICKUP
DELAY: 0.045 s
AR CO-ORD RESET
DELAY: 0.005 s
TERMINAL OPEN:
Off
AR ACCELERATE:
Off
LINE PICKUP DISTANCE
TRIP: Enabled
LINE PICKUP BLOCK:
Off
LINE PICKUP
TARGET: Self-reset
LINE PICKUP
EVENTS: Disabled
setting allows the overcurrent setting to be below the expected load current seen after
LINE PICKP UV
setting is normally enabled. It is disabled if high speed autoreclosure is
AR CO-ORD BYPASS
LINE PICKUP RCL TRIP
operand to perform a trip action if the intent is zone 1 extension.
— This setting enables and disables the line pickup feature.
— Selects the signal source for line pickup protection.
— Specifies the level of line current required to declare a line pickup operation when the line is re-
— Specifies the time during which the line is de-energized before the line pickup logic is
— Specifies the time during which the line pickup logic remains armed once the line has been
Range: 0.000 to 65.535 s in steps of 0.001
Range: Disabled, Enabled
Range: 0.000 to 65.535 s in steps of 0.001
Range: 0.000 to 65.535 s in steps of 0.001
Range: FlexLogic operand
Range: FlexLogic operand
Range: Disabled, Enabled
Range: FlexLogic operand
Range: Self-reset, Latched, Disabled
Range: Disabled, Enabled
setting that specifies the terminal status.
TERMINAL OPEN
elements resetting and blocking the trip path before the
FlexLogic operand. For security, the overcurrent trip is
VT FUSE FAIL OP
setting is provided to achieve zone
AR ACCELERATE
D60 LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
CHAPTER 5: SETTINGS
AR
operand with a 10 ms
setting.
LINE PICKUP DISTANCE TRIP