Operation Mode At Power On (Pr. 79, Pr. 340) - Mitsubishi Electric F700 Instruction Manual

Hide thumbs Also See for F700:
Table of Contents

Advertisement

Selection of operation mode and
operation location

3.17.2 Operation mode at power on (Pr. 79, Pr. 340)

When power is switched on or when power comes back on after instantaneous power failure, the inverter can
Pr. 78
page 140
be started up in network operation mode.
Pr. 80
After the inverter has started up in the network operation mode, parameter write and operation can be
page 54
performed from a program.
Pr. 339
Set this mode for communication operation using the inverter RS-485 terminals or communication option.
page 151
Pr. 341
Parameter
page 161
Number
79
Operation mode selection
Communication startup
340 *
mode selection
* The parameters can be set when Pr. 160 User group read selection = "0". However, the parameters can be set whenever the communication
option is connected. (Refer to page 140.). It can also be changed independently of the operation mode.
(1) Specify operation mode at power on (Pr. 340)
⋅ Depending on the Pr. 79 and Pr. 340 settings, the operation mode at power on (reset) changes as described below.
Pr. 340
Pr. 79
Setting
Setting
0
(initial
value)
1
2
0
(initial
3, 4
value)
6
7
0
1
2
1, 2
3, 4
*1
6
7
0
1
2
10, 12
3, 4
*1
6
7
*1
The Pr. 340 setting "2" or "12" is mainly used for communication operation using the inverter RS-485 terminals. When Pr. 57 Restart coasting
time ≠ "9999" (selection of automatic restart after instantaneous power failure), the inverter will resume the same operation state which was
in before after power has been restored from an instantaneous power failure.
*2
The operation mode cannot be switched directly between the PU operation mode and network operation mode.
*3
Operation mode can be changed between the PU operation mode and network operation mode with
and X65 signal.
♦ Parameters referred to ♦
Pr. 57 Restart coasting time
Pr. 79 Operation mode selection
150
Initial
Name
Value
0
0
Operation Mode at Power on, Power
Restoration, Reset
External operation mode
PU operation mode
External operation mode
External/PU combined operation mode
External operation mode
X12 (MRS) signal ON ....External operation mode
X12 (MRS) signal OFF ..External operation mode
NET operation mode
PU operation mode
NET operation mode
External/PU combined operation mode
NET operation mode
X12 (MRS) signal ON ....NET operation mode
X12 (MRS) signal OFF ..External operation mode
NET operation mode
PU operation mode
NET operation mode
External/PU combined operation mode
NET operation mode
External operation mode
Refer to page 109.
Refer to page 142.
Setting
Range
0 to 4, 6, 7
Select the operation mode. (Refer to page 144.)
0
As set in Pr. 79.
Started in network operation mode.
When the setting is "2", it will resume the pre-
1, 2
instantaneous power failure operation mode after an
instantaneous power failure occurs.
Started in network operation mode. Operation mode can be
changed between the PU operation mode and network
10, 12
operation mode from the operation panel. When the setting
is "12", it will resume the pre-instantaneous power failure
operation mode after an instantaneous power failure occurs.
Operation Mode Switching
Can be switched to external, PU or NET operation mode
Fixed to PU operation mode
Can be switched to external or NET operation mode
Switching to PU operation mode disabled
Operation mode switching disabled
Can be switched to external, PU or NET operation mode
with operation continued
Can be switched to external, PU or NET operation mode
Fixed to external operation mode (Forcibly switched to
external operation mode.)
Same as when Pr. 340 = "0"
Can be switched to PU or NET operation mode
Same as when Pr. 340 = "0"
Fixed to NET operation mode
Same as when Pr. 340 = "0"
Can be switched to PU or NET operation mode with
operation continued
Same as when Pr. 340 = "0"
Description
*3
*3
key of the operation panel (FR-DU07)
*2
*2