Remote Setting Function (Pr. 59) - Mitsubishi Electric F700 Instruction Manual

Hide thumbs Also See for F700:
Table of Contents

Advertisement

Frequency setting by external terminals
3.5.4

Remote setting function (Pr. 59)

Even if the operation panel is located away from the enclosure, you can use contact signals to perform
Pr. 58
continuous variable-speed operation, without using analog signals.
page 109
Pr. 60
page 118
Parameter
Number
59
Remote function selection
The above parameters can be set when Pr. 160 User group read selection = "0". (Refer to page 140)
Inverter
Forward
rotation
STF
Acceleration
RH
Deceleration
RM
Clear
RL
PC
Connection
diagram for remote setting
(1) Remote setting function
⋅ Use Pr. 59 to select whether the remote setting function is used or not and whether the frequency setting
storage function in the remote setting mode is used or not.
When Pr. 59 is set to any of "1 to 3" (remote setting function valid), the functions of the RH, RM and RL signals
are changed to acceleration (RH), deceleration (RM) and clear (RL).
⋅ When the remote function is used, the output frequency of the inverter can be compensated for as follows:
External operation ...Frequency set by RH/RM operation
PU operation .............Frequency set by RH/RM operation + PU running frequency
(2) Frequency setting storage
⋅ The frequency setting storage function stores the remote setting frequency (frequency set by RH/RM operation)
into the memory (EEPROM). When power is switched off once, then on, operation is resumed with that output
frequency value. (Pr. 59 =1)
<Frequency setting storage conditions>
⋅ Frequency at the point when the start signal (STF or STR) turns off
⋅ The remotely-set frequency is stored every one minute after one minute has elapsed since turn off (on) of
both the RH (acceleration) and RM (deceleration) signals. (The frequency is written if the present
frequency setting compared with the past frequency setting every one minute is different. The state of the
RL signal does not affect writing.)
72
Name
*
10
2
0Hz
5
Acceleration
(RH)
Deceleration
(RM)
Clear (RL)
Forward
rotation (STF)
Power supply
* External operation frequency (other than multi-speed) or PU running frequency
frequency (other than multi-speed).
(When making analog input compensation, set "1" to Pr. 28 Multi-speed input compensation
selection.
When Pr. 28 is set to "0" and acceleration/deceleration is made to reach the set frequency
of the analog voltage input (terminal 2 or terminal 4) by RH/RM, the auxiliary input by
terminal 1 becomes invalid.)
Initial Value Setting Range
0
1
2
0
3
ON
ON
ON
ON
ON
+
external running frequency or PU running
Description
RH, RM, RL
Frequency Setting
signal function
storage function
Multi-speed
setting
Remote setting
Remote setting
(Turning STF/STR
Remote setting
off clears remote
setting frequency.)
When Pr. 59 = 1
When Pr. 59 = 1, 2
When Pr. 59 = 3
When Pr. 59 = 2, 3
ON
ON
ON
ON
Yes
No
No
Time
ON
ON