3.3 Limit the output frequency

Purpose
Set upper limit and lower limit of
output frequency
Perform operation by avoiding
machine resonance points
3.3.1

Maximum/minimum frequency (Pr. 1, Pr. 2, Pr. 18)

You can limit the motor speed. Clamp the upper and lower limits of the output frequency.
Pr. 0
page 53
Pr. 3
Parameter
page 64
Number
Pr. 17
page 87
Pr. 19
1
Maximum frequency
page 64
2
Minimum frequency
High speed maximum
18 *
frequency
* The parameters can be set when Pr. 160 User group read selection = "0". (Refer to page 140)
Output frequency
(Hz)
Pr.1
Pr.18
Pr.2
0
(4mA)
Clamped at the
minimum frequency
REMARKS
⋅ When performing operation above 60Hz using the frequency setting analog signal, change Pr. 125 (Pr. 126) (frequency setting
gain). If only Pr. 1 or Pr. 18 is changed, operation above 60Hz cannot be performed
(2) Set minimum frequency
⋅ Use Pr. 2 Minimum frequency to set the lower limit of the output frequency.
⋅ The output frequency is clamped by the Pr. 2 setting even the set frequency is lower than the Pr. 2 setting (The
frequency will not decrease to the Pr. 2 setting.)
REMARKS
⋅ When Pr. 15 Jog frequency is equal to or less than Pr. 2, the Pr.15 setting has precedence over the Pr. 2 setting.
⋅ When stall prevention is activated to decrease the output frequency, the output frequency may drop to Pr. 2 or below.
If the Pr. 2 setting is higher than the Pr. 13 Starting frequency value, note that the motor will run at the set
frequency according to the acceleration time setting by merely switching the start signal on, without entry of
the command frequency.
♦ Parameters referred to ♦
Pr. 13 Starting frequency
Pr. 15 Jog frequency
Pr. 125Terminal 2 frequency setting gain frequency, Pr. 126 Terminal 4 frequency setting gain frequency
62
Maximum/minimum
frequency
Frequency jump
Name
01160
or less
01800
or more
01160
or less
01800
or more
Clamped at the
maximum frequency
Frequency setting
5, 10V
(20mA)
Refer to page 76
Refer to page 69
Parameter that must be set
Pr. 1, Pr. 2, Pr. 18
Initial Value
Setting Range
120Hz
0 to 120Hz
60Hz
0Hz
0 to 120Hz
120Hz
120 to 400Hz
60Hz
(1) Set maximum frequency
⋅ Set the upper limit of the output frequency in Pr. 1 Maximum
frequency. If the frequency of the frequency command entered
is higher than the setting, the output frequency is clamped at
the maximum frequency.
⋅ When you want to perform operation above 120Hz, set the
upper limit of the output frequency to Pr. 18 High speed maximum
frequency. (When Pr. 18 is set, Pr. 1 automatically switches to
the frequency of Pr. 18. When Pr. 18 is set, Pr. 18 automatically
switches to the frequency of Pr. 1.)
Caution
Refer to Page
Pr. 31 to Pr. 36
Description
Set the upper limit of the output
frequency.
Set the lower limit of the output
frequency.
Set when performing the operation
at 120Hz or more.
Refer to page 129