(11) Switching of operation mode by external terminal (X65, X66 signal)
⋅ When Pr. 79 = any of "0, 2, 6, 7", the operation mode switching signals (X65, X66) can be used to change the
PU or external operation mode to network operation mode during a stop (during a motor stop or start command
off). (Pr. 79 = "6" switch-over mode can be changed during operation)
⋅ When switching between the network operation mode and PU operation mode
1) Set Pr. 79 to "0" (initial value), "6" or "7". (At the Pr. 79 setting of "7", the operation mode can be switched when the
X12 (MRS) signal turns on.)
2) Set "10 or 12" in Pr. 340 Communication startup mode selection.
3) Set "65" to any of Pr. 178 to Pr. 189 to assign the NET-PU operation switching signal (X65) to the external terminal.
4) The operation mode changes to PU operation mode when the X65 signal turns on, or to network operation mode
when the X65 signal turns off.
Pr. 340
Pr. 79
Setting
Setting
0
(initial value)
1
2
3, 4
10, 12
6
X12(MRS)
ON
7
X12(MRS)
OFF
*1
NET operation mode when the X66 signal is on.
*2
PU operation mode when the X16 signal is off. PU operation mode also when Pr. 550 NET mode operation command source selection = "1"
(communication option control source) and the communication option is not fitted.
*3
External operation mode when the X16 signal is on.
⋅ When switching between the network operation mode and external operation mode
1) Set Pr. 79 to "0" (initial value), "2", "6" or "7". (At the Pr. 79 setting of "7", the operation mode can be switched when
the X12 (MRS) signal turns on.)
2) Set "0 (initial value), 1 or 2" in Pr. 340 Communication startup mode selection.
3) Set "66" to any of Pr. 178 to Pr. 189 to assign the NET-external operation switching signal (X66) to the external
terminal.
4) The operation mode changes to network operationmode when the X66 signal turns on, or to external operation
mode when the X66 signal turns off.
Pr. 340
Pr. 79
Setting
Setting
0
(initial value)
1
2
0
3, 4
,
(initial value)
6
1, 2
X12(MRS)
ON
7
X12(MRS)
OFF
*1
PU operation mode also when Pr. 550
communication option is not fitted.
*2
PU operation mode when the X16 signal is off. When the X65 signal has been assigned, the operation mode changes with the ON/OFF state of the
X65 signal.
REMARKS
⋅ The priorities of Pr. 79, Pr. 340 and signals are Pr. 79 > X12 > X66 > X65 > X16 > Pr. 340.
CAUTION
⋅ Changing the terminal assignment using Pr. 178 to Pr. 189 (input terminal function selection) may affect the other functions.
Please make setting after confirming the function of each terminal.
♦ Parameters referred to ♦
Pr. 15 Jog frequency
Refer to page 69.
Pr. 4 to 6, Pr. 24 to 27, Pr. 232 to Pr. 239 Multi-speed operation
Pr. 75 Reset selection/disconnected PU detection/PU stop selection
Pr. 161 Frequency setting/key lock operation selection
Pr. 178 to Pr. 189 (Input terminal function selection)
Pr. 340 Communication startup mode selection
Pr. 550 NET mode operation command source selection
X65 Signal State
ON (PU)
PU operation mode
NET operation mode
*1
PU operation mode
NET operation mode
External/PU combined operation mode
NET operation mode
PU operation mode
*1
PU operation mode
NET operation mode
*1
External operation mode
X66 signal state
ON (NET)
NET operation mode
External operation mode
*1
PU operation mode
External operation mode
NET operation mode
*1
External/PU combined operation mode
NET operation mode
External operation mode
*1
NET operation mode
External operation mode
*1
External operation mode
NET mode operation command source selection = "1" (communication option control source) and the
Refer to page 217.
Refer to page 85.
Refer to page 150.
Refer to page 151.
Selection of operation mode and
OFF (NET)
Cannot be switched to external operation mode
*2
Fixed to PU operation mode
Fixed to NET operation mode
External/PU combined mode fixed
Operation mode can be switched with operation continued
*2
Cannot be switched to external operation mode
Output stop in external operation mode
*2, 3
Forcibly switched to external operation mode
OFF(external)
*2
Fixed to PU operation mode
Cannot be switched to PU operation mode
External/PU combined mode fixed
Operation mode can be switched with operation continued
*2
Output stop in external operation mode
*2
Forcibly switched to external operation mode
Refer to page 67.
Refer to page 136.
operation location
Remarks
Remarks
149
3