Selection of operation mode and
operation location

3.17.2 Operation mode at power on (Pr. 79, Pr. 340)

When power is switched on or when power comes back on after instantaneous power failure, the inverter can be
Pr. 78
started up in network operation mode.
page 146
After the inverter has started up in the network operation mode, parameter write and operation can be performed
Pr. 80
page 58
from a program.
Pr. 339
Set this mode for communication operation using the RS-485 terminals or communication option.
page 157
Parameter
Pr. 341
Number
page 167
79
Operation mode selection
Communication startup
340 *
mode selection
* The above parameters can be changed during a stop in any operation mode.
* The parameters can be set when Pr. 160 User group read selection = "0". However, the parameters can be set whenever the communication option
is connected. (Refer to page 146.).
(1) Specify operation mode at power on (Pr. 340)
⋅ Depending on the Pr. 79 and Pr. 340 settings, the operation mode at power on (reset) changes as described below.
Pr. 340
Pr. 79
Setting
Setting
0
(initial
value)
1
2
0
(initial
3, 4
value)
6
7
0
1
2
1, 2
3, 4
*1
6
7
0
1
2
10, 12
3, 4
*1
6
7
*1
The Pr. 340 setting "2" or "12" is mainly used for communication operation using the inverter RS-485 terminals. When a value other than "9999"
(selection of automatic restart after instantaneous power failure) is set in Pr. 57 Restart coasting time, the inverter will resume the same operation
state which was in before after power has been restored from an instantaneous power failure.
*2
The operation mode cannot be switched directly between the PU operation mode and network operation mode.
*3
Operation mode can be changed between the PU operation mode and network operation mode with
X65 signal.
♦ Parameters referred to ♦
Pr. 57 Restart coasting time
Pr. 79 Operation mode selection
156
Initial
Name
Value
0
0
Operation Mode at Power on, Power
Restoration, Reset
External operation mode
PU operation mode
External operation mode
External/PU combined operation mode
External operation mode
X12 (MRS) signal ON ....External operation mode
X12 (MRS) signal OFF ..External operation mode
NET operation mode
PU operation mode
NET operation mode
External/PU combined operation mode
NET operation mode
X12 (MRS) signal ON ....NET operation mode
X12 (MRS) signal OFF ..External operation mode
NET operation mode
PU operation mode
NET operation mode
External/PU combined operation mode
NET operation mode
External operation mode
Refer to page 114.
Refer to page 148.
Setting
Range
0 to 4, 6, 7
Select the operation mode. (Refer to page 150.)
0
As set in Pr. 79.
Started in network operation mode.
When the setting is "2", it will resume the pre-instantaneous
1, 2
power failure operation mode after an instantaneous power
failure occurs.
Started in network operation mode. Operation mode can be
changed between the PU operation mode and network
10, 12
operation mode from the operation panel. When the setting is
"12", it will resume the pre-instantaneous power failure
operation mode after an instantaneous power failure occurs.
Switching among the external, PU, and NET operation
mode is enabled
Fixed to PU operation mode
Switching between the external and Net operation mode is enabled
Switching to PU operation mode is disabled
Operation mode switching is disabled
Switching among the external, PU, and NET operation
mode is enabled with operation continued
Switching among the external, PU, and NET operation
mode is enabled
Fixed to external operation mode (Forcibly switched to
external operation mode.)
Same as when Pr. 340 = "0"
Switching between the PU and NET operation mode is enabled
Same as when Pr. 340 = "0"
Fixed to NET operation mode
Same as when Pr. 340 = "0"
Switching among the external, PU, and NET operation
mode is enabled with operation continued
Same as when Pr. 340 = "0"
Description
Operation Mode Switching
*2
*2
*3
key of the operation panel (FR-DU07) and
*3