4.6.4 Motor rotates in opposite direction

Check that the phase sequence of output terminals U, V and W is correct.
Check that the start signals (forward rotation, reverse rotation) are connected properly. (Refer to
page 89)

4.6.5 Speed greatly differs from the setting

Check that the frequency setting signal is correct. (Measure the input signal level.)
Check that Pr.1, Pr.2, Calibration parameter C2 to C7 settings are correct
Check that the input signal lines are not affected by external noise.
(Use shielded cables)
Check that the load is not too heavy.
Check that the Pr. 31 to Pr. 36 (frequency jump) settings are correct.

4.6.6 Acceleration/deceleration is not smooth

Check that the acceleration and deceleration time settings are not too short.
Check that the load is not too heavy.

4.6.7 Motor current is large

Check that the load is not too heavy.
Check that the Pr.0 Torque boost setting is correct.
Check that the Pr.3 Base frequency setting is correct.
Check that the Pr.19 Base frequency voltage is correct

4.6.8 Speed does not increase

Check that the maximum frequency (Pr. 1) setting is correct. (If you want to run the motor at 120Hz
or more, set Pr.18 High speed maximum frequency. (Refer to page 62.)
Check that the load is not too heavy.
(In agitators, etc., load may become heavier in winter.)
Check that the brake resistor is not connected to terminals P/+-P1 accidentally.

4.6.9 Speed varies during operation

1) Inspection of load
Check that the load is not varying.
2) Check the input signals
Check that the frequency setting signal is not varying.
Check that the frequency setting signal is not affected by noise.
Check for a malfunction due to undesirable currents when the transistor output unit is connected.
(Refer to page 17)
3) Others
Check that the wiring length is not too long for V/F control

4.6.10 Operation panel (FR-DU07) display is not operating

Check that the operation panel is connected to the inverter securely.

4.6.11 Parameter write cannot be performed

Make sure that operation is not being performed (signal STF or STR is not ON).
Make sure that you are not attempting to set the parameter in the external operation mode.
Check Pr.77 Parameter write selection.
Check Pr.161 Frequency setting/key lock operation selection.
Check first when you have troubles.