(6) Switching of command source by external terminal (X67)
⋅ In network operation mode, the command source switching signal (X67) can be used to switch the operation
command source and speed command source. This signal can be utilized to control the signal input from both
the external terminal and communication.
⋅ Set "67" to any of Pr. 178 to Pr. 186 to assign the X67 signal to the external terminal.
⋅ When the X67 signal is off, the operation command source and speed command source are external.
X67 Signal State
No signal assignment
ON
OFF
REMARKS
⋅ The ON/OFF state of the X67 signal is reflected only during a stop. It is reflected after a stop when the terminal is switched
during operation.
⋅ When the X67 signal is off, a reset via communication is disabled.
♦ Parameters referred to ♦
Pr. 28 Multi-speed input compensation selection
Pr. 59 Remote function selection
Pr. 79 Operation mode selection
Operation Command Source
According to Pr. 338
Operation is valid only from external terminal signal.
Refer to page 71.
Refer to page 72.
Refer to page 142.
Selection of operation mode and
operation location
Speed Command Source
According to Pr. 339