1.3 Main circuit terminal specifications

1.3.1

Specification of main circuit terminal

Terminal
Terminal Name
Symbol
R/L1,
S/L2,
AC power input
T/L3
U, V, W
Inverter output
R1/L11,
Power supply for
S1/L21
control circuit
Brake unit
P/+, N/-
connection
DC reactor
P/+, P1
connection
PR, PX
Please do not remove or use terminals PR and PX or the jumper connected.
Earth
1.3.2
Terminal arrangement of the main circuit terminal, power supply and the
motor wiring.
400V class
FR-F740-00023 to 00126-EC
Screw size (M4)
R/L1 S/L2 T/L3
Jumper
R1/L11 S1/L21
IM
Motor
Power supply
Connect to the commercial power supply.
Keep these terminals open when using the high power factor converter
(FR-HC, MT-HC) or power regeneration common converter (FR-CV).
Connect a three-phase squirrel-cage motor.
Connected to the AC power supply terminals R/L1 and S/L2. To retain
the alarm display and alarm output or when using the high power factor
converter (FR-HC, MT-HC) or power regeneration common converter
(FR-CV), remove the jumpers from terminals R/L1-R1/L11 and S/L2-
S1/L21 and apply external power to these terminals.
Do not turn off the power supply for control circuit (R1/L11, S1/L21) with
the main circuit power (R/L1, S/L2, T/L3) on. Doing so may damage the
inverter. The circuit should be configured so that the main circuit power
(R/L1, S/L2, T/L3) is also turned off when the power supply for control
circuit (R1/L11, S1/L21) is off.
00380 or less : 60VA, 00470 to 02160 : 80VA
Connect the brake unit (FR-BU, BU and MT-BU5), power
regeneration common converter (FR-CV), high power factor
converter (FR-HC and MT-HC) or power regeneration converter (MT-
RC).
For the 01160 or less, remove the jumper across terminals P/+ - P1
and connect the DC reactor. (For the 01800 or more, a DC reactor
is standard-equipped.)
For earthing the inverter chassis. Must be earthed.
Jumper
P/+ PR
N/-
PX
Screw size
Charge lamp
(M4)

Main circuit terminal specifications

Description
FR-F740-00170, 00250-EC
Jumper
R1/L11 S1/L21
Screw size
(M4)
R/L1 S/L2 T/L3
Power supply
Charge lamp
N/-
P/+ PR
Jumper
PX
IM
Motor
Screw size
(M4)
1
5