Misoperation Prevention And Parameter Setting Restriction; Reset Selection/Disconnected Pu Detection/Pu Stop Selection (Pr.75) - Mitsubishi Electric F700 Instruction Manual

Hide thumbs Also See for F700:
Table of Contents

Advertisement

Misoperation prevention and parameter
setting restriction

3.16 Misoperation prevention and parameter setting restriction

Purpose
Limit reset function
Make alarm stop when PU is disconnected
Stop from PU
Prevention of parameter rewrite
Prevention of reverse rotation of the
motor
Display necessary parameters
Control of parameter write by
communication

3.16.1 Reset selection/disconnected PU detection/PU stop selection (Pr.75)

You can select the reset input acceptance, disconnected PU (FR-DU07) connector detection function and PU
Pr.74
stop function.
page 128
Pr.76
page 116
Parameter
Number
Reset selection/disconnected
75
PU detection/PU stop selection
⋅The above parameters can be set when Pr. 160 User group read selection = "0". (Refer to page 140)
⋅The Pr. 75 value can be set any time. Also, if parameter (all) clear is executed, this setting will not return to the initial value.
Pr.75
Setting
0
Reset input normally enabled.
Enabled only when the protective
1
function is activated
2
Reset input normally enabled.
Enabled only when the protective
3
function is activated
14
(initial
Reset input normally enabled.
value)
Enabled only when the protective
15
function is activated
16
Reset input normally enabled.
Enabled only when the protective
17
function is activated
100
Reset input normally enabled.
Enabled only when the protective
101
function is activated
102
Reset input normally enabled.
Enabled only when the protective
103
function is activated
114
Reset input normally enabled.
Enabled only when the protective
115
function is activated
116
Reset input normally enabled.
Enabled only when the protective
117
function is activated
136
Reset selection/
disconnected PU detection/
PU stop selection
Parameter write disable
selection
Reverse rotation prevention
selection
Display of applied
parameters and user group
function
EEPROM write selection
Name
Reset Selection
Parameter that must be set
Initial
Setting Range
Value
01160 or
0 to 3, 14 to 17
less
14
0 to 3, 14 to 17,
01800 or
100 to 103,
more
114 to117
Disconnected PU
Detection
If the PU is disconnected,
operation will be continued.
When the PU is
disconnected, the inverter
output is shut off.
If the PU is disconnected,
operation will be continued.
When the PU is
disconnected, the inverter
output is shut off.
If the PU is disconnected,
operation will be continued.
When the PU is
disconnected, the inverter
output is shut off.
If the PU is disconnected,
operation will be continued.
When the PU is
disconnected, the inverter
output is shut off.
Pr. 75
Pr. 77
Pr. 78
Pr.160, Pr.172 to Pr.174
Pr.342
Description
For the initial value, reset always
enabled, without disconnected PU
detection, and with PU stop function
are set.
PU Stop Selection
Pressing
decelerates
the motor to a stop only in
the PU operation mode.
Pressing
decelerates
the motor to a stop in any of
the PU, external and
communication operation
modes.
Pressing
decelerates
the motor to a stop only in
the PU operation mode.
Pressing
decelerates
the motor to a stop in any of
the PU, external and
communication operation
modes.
Refer to
page
136
139
140
140
162
Reset Limit
(01800 or less)
Not function
Function

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents