Energy Saving Monitor (Pr. 891 To Pr. 899) - Mitsubishi Electric F700 Instruction Manual

Hide thumbs Also See for F700:
Table of Contents

Advertisement

3.13.2 Energy saving monitor (Pr. 891 to Pr. 899)

From the power consumption estimated value during commercial power supply operation, the energy saving
effect by use of the inverter can be monitored/output.
Parameter
Name
Number
DU/PU main display data
52
selection
CA terminal function
54
selection
AM terminal function
158
selection
Cumulative power monitor
891
digit shifted times
892
Load factor
Energy saving monitor
893
reference (motor capacity)
Control selection during
894
commercial power-supply
operation
Power saving rate reference
895
value
896
Power unit cost
Power saving monitor
897
average time
Power saving cumulative
898
monitor clear
Operation time rate
899
(estimated value)
The above parameters can be set when Pr. 160 User group read selection = "0". (Refer to page 140)
The above parameters allow its setting to be changed during operation in any operation mode even if "0" (initial value) is set in Pr. 77 Parameter
write selection.
Energy saving operation and energy saving monitor
Initial Value
Setting Range
0
0, 5, 6, 8 to 14, 17, 20, 23
(output
to 25, 50 to 57, 100
frequency)
1
1 to 3, 5, 6, 8 to 14, 17,
(output
21, 24, 50, 52, 53
frequency)
0 to 4
9999
9999
100%
30 to 150%
01160 or
SLD/LD value
less
of Applied
01800 or
moter Capacity
more
0
1
0
2
3
0
9999
1
9999
0 to 500
9999
9999
0
9999
1 to 1000h
9999
0
1
10
9999
9999
0 to 100%
9999
9999
Description
50:Power saving monitor
51:Cumulative saving power
monitor
50:Power saving monitor
Set the number of times to shift the
cumulative power monitor digit
Clamp the monitoring value at
maximum.
No shift
Clear the monitor value when it
exceeds the maximum value.
Set the load factor for commercial
power-supply operation. Multiplied
by the power consumption rate
(page 122) during commercial
power supply operation.
Set the motor capacity (pump
0.1 to 55kW
capacity). Set when calculating
power saving rate, average power
0 to
saving rate value, commercial
3600kW
operation power.
Discharge damper control (fan)
Inlet damper control (fan)
Valve control (pump)
Commercial power-supply drive
(fixed value)
Consider the value during
commercial power-supply
operation as 100%
Consider the Pr. 893 setting as
100%.
No function
Set the power unit cost. Display
the power saving amount charge
on the energy saving monitor.
No function
Average for 30 minutes
Average for the set time
No function
Cumulative monitor value clear
Cumulative monitor value hold
Totalization continued
(communication data upper limit
9999)
Totalization continued
(communication data upper limit
65535)
Use for calculation of annual
power saving amount. Set the
annual operation ratio (consider
365 days × 24hr as 100%).
No function
Pr.51
page 78
Pr. 55
page 104
Pr.157
page 56
Pr.159
page 192
Pr.889
page 216
Pr. 990
page 219
3