(2) PU connector communication system configuration and wiring
System configuration
FR-DU07
Operation
panel
connector
connector
FR-ADP
(option)
RJ-45 connector 2)
10BASE-T cable 1)
Connection with RS-485 computer
Computer Side Terminals
Signal name
RDA
RDB
SDA
SDB
RSA
Request to send
RSB
Request to send
CSA
Clear to send
CSB
Clear to send
SG
Signal ground
FG
Frame ground
* Make connections in accordance with the manual of the computer used. Fully check the terminal numbers of the computer
since they change with the model.
REMARKS
⋅ Computer-inverter connection cable
Refer to the following for the cable (RS-232C ⇔ RS-485 converter) for connection of the computer having the RS-
232C interface with the inverter. Commercially available product examples (as of April, 2004)
* The converter cable cannot connect two or more inverters (the computer and inverter are connected on a 1:1 basis).
Since the product is packed with the RS-232C cable and RS-485 cable (10BASE-T + RJ-45 connector), the cable and
connector need not be prepared separately. Contact a maker for details of the product.
⋅ Refer to the following when fabricating the cable on the user side.
Commercially available product examples (as of April, 2004)
1) 10BASE-T cable SGLPEV-T 0.5mm × 4P * Mitsubishi Cable Industries, Ltd.
* Do not use pins No. 2, 8 of the 10- BASE-T cable.
CAUTION
When performing RS-485 communication with multiple inverters, use the RS-485 terminal. (Refer to page 159)
Computer
Inverter
PU
RS-485
interface/
terminals
RJ-45 connector 2)
Cable connection and signal direction
Description
Receive data
Receive data
Send data
Send data
Type
FA-T-RS40
*
Product
Type
Communication operation and setting
Station 0
Computer
Inverter
RS-232C
connector
RS-232C
PU
cable
connector
RS-232C-RS-485
converter
RJ-45
connector 2)
10BASE-T cable 1)
10BASE-T cable
*
0.3mm
2
or more
Maker
Mitsubishi Electric Engineering Co., Ltd.
Maker
Station 0
Inverter
PU
Maximum
connector
15m
RJ-45
connector
2)
10BASE-T cable 1)
Inverter
PU connector
RS-485 block
SDA
SDB
RDA
RDB
SG