Misoperation prevention and parameter
setting restriction

3.16 Misoperation prevention and parameter setting restriction

Purpose
Limit reset function
Make alarm stop when PU is disconnected
Stop from PU
Prevention of parameter rewrite
Prevention of reverse rotation of the
motor
Display necessary parameters
Control of parameter write by
communication

3.16.1 Reset selection/disconnected PU detection/PU stop selection (Pr. 75)

You can select the reset input acceptance, disconnected PU (FR-DU07/FR-PU04) connector detection function
Pr.74
and PU stop function.
page 134
Pr.76
Parameter
page 122
Number
Reset selection/disconnected
75
PU detection/PU stop selection
⋅The above parameters can be set when Pr. 160 User group read selection = "0". (Refer to page 146)
⋅The Pr. 75 value can be set any time. Also, if parameter (all) clear is executed, this setting will not return to the initial value.
Pr. 75
Setting
0
Reset input always enabled
Enabled only when the protective
1
function is activated
2
Reset input always enabled
Enabled only when the protective
3
function is activated
14
(initial
Reset input always enabled
value)
Enabled only when the protective
15
function is activated
16
Reset input always enabled
Enabled only when the protective
17
function is activated
100
Reset input always enabled
Enabled only when the protective
101
function is activated
102
Reset input always enabled
Enabled only when the protective
103
function is activated
114
Reset input always enabled
Enabled only when the protective
115
function is activated
116
Reset input always enabled
Enabled only when the protective
117
function is activated
142
Reset selection/disconnected
PU detection/PU stop selection
Parameter write selection
Reverse rotation prevention
selection
Display of applied parameters
and user group function
EEPROM write selection
Initial
Name
Value
Reset Selection
Parameter that must be Set
Setting Range
01160 or
0 to 3, 14 to 17
less
14
0 to 3, 14 to 17,
01800 or
100 to 103,
more
114 to117
Disconnected PU
Detection
If the PU is disconnected,
operation will be continued.
When the PU is
disconnected, the inverter
output is shut off.
If the PU is disconnected,
operation will be continued.
When the PU is
disconnected, the inverter
output is shut off.
If the PU is disconnected,
operation will be continued.
When the PU is
disconnected, the inverter
output is shut off.
If the PU is disconnected,
operation will be continued.
When the PU is
disconnected, the inverter
output is shut off.
Pr. 75
Pr. 77
Pr. 78
Pr. 160, Pr. 172 to Pr. 174
Pr. 342
Description
For the initial value, reset always enabled,
without disconnected PU detection, and
with PU stop function are set.
PU Stop Selection
Pressing
decelerates
the motor to a stop only in
the PU operation mode.
Pressing
decelerates
the motor to a stop in any of
the PU, external and
communication operation
modes.
Pressing
decelerates
the motor to a stop only in
the PU operation mode.
Pressing
decelerates
the motor to a stop in any of
the PU, external and
communication operation
modes.
Refer to
Page
142
145
146
146
168
Reset Limit
(01800 or more)
Not function
Function